Final | 10/4/2019 | 10/7/2019 | 10/7/2019 | A | PASS |
Rock A. Hudson
|
|
|
Out side electric boxes/ temp power removed Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
|
Final | 10/1/2019 | 10/2/2019 | 10/2/2019 | A | PART |
Rock A. Hudson
|
|
|
Final inspection for Unit #406. Contact John (Homey) McElroy. Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Items remaining- 590.6(B)-Temp service has no GFCI protection on 50 amp receptacles, Remove or make compliant. 314.20- All boxes shall have wall cover complete around them to prevent water from entering box or structure. 314.25- All boxes and enclosures shall have covers. Level 3 heat tape panel and level 3 patio switch. Unit 506 has been permitted seperately. 406 TCO ok
|
Final | 9/19/2019 | 9/20/2019 | 9/20/2019 | A | PART |
Rock A. Hudson
|
|
|
Final inspection for Units 406, 507, 509, 511, 512, north stairs/roof/pent house/3rd floor patio/2nd floor court yard Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Items remaining- 1- 110.3- Level 2 court yard planter ground boxes shall have wire connectors listed for wet locations. 2- 210.8(B)- Level 3 patio disposal receptacle located outdoors shall have GFCI protection. 2 pole 50 amp receptacle in garage shall have GFCI protection. 3- 314.15- All exterior boxes shall be sealed to prevent moisture from entering box or wall. 4- 590.6(B)- All temp power shall have GFCI protection. All 250 receptacles need it.
This TCO is for construction personel still only allowed access. Signed off podium and phase 2 permits for TCO ok 3-
|
Change Status to I | | | 9/19/2019 | | DONE |
|
|
|
per Rock electrical inspector this was final accidently so it was put back into ISS status
|
Final | 9/17/2019 | 9/18/2019 | 9/18/2019 | A | PART |
Rock A. Hudson
|
|
|
Final Inspection for Units 203, 513, 514, and 515. Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in office. TCO ok
|
Telephone call | | | 9/18/2019 | | DONE |
|
|
|
Received revised certificate of value from Lea Electric to split out permit for garge, se ELE19-03533
|
Final | 9/16/2019 | 9/17/2019 | 9/17/2019 | A | PASS |
Rock A. Hudson
|
|
|
Final inspections for - Unit 309, and 204 5th floor hall, 5th floor trash room, 5th com room, 4th floor hall 4th floor trash room, 4th floor com. Room and south stairs // Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted, added level 1 TI vanilla space TCO ok
|
Final | 9/12/2019 | 9/13/2019 | 9/13/2019 | A | PART |
Rock A. Hudson
|
|
|
Final inspections for 2nd floor hall, 2nd floor trash room, 2nd floor com room, 3rd floor hall, 3rd floor trash room, 3rd floor bath room, 3rd floor com room. Contact electrician on-site - John (Homey) McElroy Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek *406 will need TCO prior to appliances being set. All electrical to be safed off and appliances to be set prior to actual final date. *506 to be removed from this permit and to be permitted seperately. Level 3 bathroom heater cover not in place. Rest of list signed off in office. TCO ok
|
Final | 9/11/2019 | 9/12/2019 | 9/12/2019 | A | PART |
Rock A. Hudson
|
|
|
Final Inspection for Units 307, 306, 409, and 407 Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in office. TCO ok
|
Final | 9/10/2019 | 9/11/2019 | 9/11/2019 | A | PART |
Rock A. Hudson
|
|
|
Final inspection for Units 411,412,413,414, and 415 Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in office. TCO ok
|
Final | 9/9/2019 | 9/10/2019 | 9/10/2019 | A | PART |
Rock A. Hudson
|
|
|
Final for Units 311, 312, 313, 314, and 315. Contact John (Homey) McElroy. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in offce. TCO ok
|
Final | 9/5/2019 | 9/6/2019 | 9/6/2019 | A | PART |
Rock A. Hudson
|
|
|
Final inspection for units 206, 207, and 209 Contact electrician on-site John McElroy (Homey) Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in office. TCO ok
|
Final | 9/4/2019 | 9/5/2019 | 9/5/2019 | A | PART |
Rock A. Hudson
|
|
|
Final inspection for Units 211, 212, 213, 214, and 215 Contact electrician onsite - John McElroy (Homey) Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted sugned off in office, TCO ok
|
Electrical Rough-In | 8/23/2019 | 8/26/2019 | 8/26/2019 | A | PASS |
Rock A. Hudson
|
|
|
John Phone #: ###-#### All levels server room drop lids, Level 3 public bathroom droplid, must have larger access, Level 4 406 floor heat rough in ok cover
|
Electrical Rough-In | 8/20/2019 | 8/21/2019 | 8/21/2019 | A | PASS |
Rock A. Hudson
|
|
|
hallway ceilings on the 2nd, 3rd, 4th and 5th floor Rough in for Cover- Contact John (Homey) McElroy Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek Corridors complete, last soffit levels 2, 3, 4, 5 rough in ok cover
|
Final | 8/9/2019 | 8/12/2019 | 8/12/2019 | A | PART |
Rock A. Hudson
|
|
|
Final for Units 201 ; 202 only Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek In future check lockouts for hood and micro, and circuit directory for 201,202. Sign off in office when done. Egress not complete. Units noted only TCO ok
|
Electrical Rough-In | 8/7/2019 | 8/7/2019 | 8/7/2019 | A | PASS |
Rock A. Hudson
|
|
|
Parking Garage Ceiling Rough in for Cover Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Basement, dag wash, bike rm, trash rm, trash entry soffit ceilings rough in ok cover.
|
Electrical Rough-In | 8/5/2019 | 8/6/2019 | 8/6/2019 | A | PASS |
Rock A. Hudson
|
|
|
Floors 2nd,3rd,4th,and 5th Trash Room Rough in Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Levels noted trash rm ceilings and level 5 corridor complete rough in ok cover
|
Electrical Rough-In | 7/19/2019 | 7/22/2019 | 7/22/2019 | A | PASS |
Rock A. Hudson
|
|
|
Rough-in Inspection for trash rooms on 2nd,3rd,4th, and 5th floors. Contact John (Homey) McElroy. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted rough in ok cover
|
Electrical Rough-In | 7/15/2019 | 7/16/2019 | 7/16/2019 | A | PASS |
Rock A. Hudson
|
|
|
North Half - 5th Floor Hall Ceiling Inspection Contact electrician John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek North and south corridor ceiling to center stair rough in ok cover
|
Electrical Rough-In | 7/10/2019 | 7/11/2019 | 7/11/2019 | A | PASS |
Rock A. Hudson
|
|
|
Unit 506 drop ceiling rough in inspection Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Room noted powder bath and fireplace not ready and rest of drop ceilings rough in ok cover
|
Electrical Rough-In | 6/28/2019 | 7/1/2019 | 7/1/2019 | A | PASS |
Daryl DeGrange
|
|
|
Unit 307 heat mat Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek UL Listed heat mat R/I OK cover
|
Electrical Rough-In | 6/27/2019 | 6/28/2019 | 6/28/2019 | A | PASS |
Daryl DeGrange
|
|
|
Storage Unit ceiling cover Contact electrician on site John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek rough-in ok cover
|
Electrical Rough-In | 6/25/2019 | 6/26/2019 | 6/26/2019 | A | CANC |
Eric Story
|
|
|
Rough in Heated floor mat for Unit 307 Contact John (Homey) McElroy Thank you, Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek
|
Electrical Rough-In | 6/12/2019 | 6/13/2019 | 6/13/2019 | A | PASS |
Rock A. Hudson
|
|
|
Unit 406 drop ceiling rough in. Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 406 fire place and drop lids rough in ok cover
|
Electrical Rough-In | 6/3/2019 | 6/4/2019 | 6/4/2019 | A | PASS |
Rock A. Hudson
|
|
|
4th floor hall drop ceiling rough-in for cover. Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Area noted rough in ok cover.
|
Electrical Rough-In | 5/28/2019 | 5/29/2019 | 5/29/2019 | A | PASS |
Rock A. Hudson
|
|
|
Drop-ceiling rough-in inspection for units #507 ; 509 Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek 506 Wine bar receptacles,507, 509 drop lids rough in ok cover
|
Electrical Rough-In | 5/16/2019 | 5/17/2019 | 5/17/2019 | A | PASS |
Rock A. Hudson
|
|
|
Rough in for Unit 506 and Drop ceiling for Unit 204 Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 210.52(C)(1)- Wine bar located in nook area shall have receptacle outlets installed to serve counter top space so no point measured along wall line is more than 24" from a receptacle outlet. Will verify on final. 204 drop lids and 506 rough in ok cover
|
Electrical Rough-In | 5/15/2019 | 5/16/2019 | 5/16/2019 | A | PASS |
Rock A. Hudson
|
|
|
Inspection for the planters. Contact John (Homey) McElroy. Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Level 2 courtyard north wall and N.E. planter rough in ok cover
|
Electrical Rough-In | 5/13/2019 | 5/13/2019 | 5/13/2019 | P | PASS |
Rock A. Hudson
|
|
|
5TH floor units ceiling drops. Unit 515/513/511/514/512 fire place Pent house trash room 3rd floor corridor lights Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Level 3 corridor drop lids, level 5 units 511, 512, 513, 514, 515, fire place in 512 and penthouse trash room rough in ok cover
|
Electrical Rough-In | 5/2/2019 | 5/3/2019 | 5/3/2019 | A | PASS |
Rock A. Hudson
|
|
|
Unit 412 fire place Unit 407 fire place 2nd floor hall way Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Discussed LED rope or tape lighting to penatrate ceiling to get to other side of bathroom would depend on manufacturers instructions if approved for such installation. Each bathroom receptacle is fed by dedicated circuits so could have LED lighting on with basin receptacle as per 210.11(C)(3). Units 407and 412 fireplaces and level 2 hall ceilings rough in ok cover.
|
Electrical Rough-In | 4/26/2019 | 4/29/2019 | 4/29/2019 | A | PASS |
Rock A. Hudson
|
|
|
Electrical Rough-In for Unit #204 Contact John McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Unit noted rough in ok cover
|
Electrical Rough-In | 4/17/2019 | 4/18/2019 | 4/18/2019 | A | PASS |
Rock A. Hudson
|
|
|
Drop ceilings units 407 , 409 and one planter Call John Phone #: ###-#### Inspection requested via web by Tom Betty Discussed unit 506 island. Kitchen island shall be a undivided space as per 210.52(C)(4). Area behind sink is greater than 12" in depth so shall be undivided space. A minimum of 1 receptacle outlet could serve island counter top space. Units noted drop lids and S.E. planter pour rough in ok cover
|
Electrical Rough-In | 4/12/2019 | 4/15/2019 | 4/15/2019 | A | PASS |
Rock A. Hudson
|
|
|
Units 411 , 412 , 413 , 414 and 415 Call John Phone #: ###-#### Inspection requested via web by Tom Betty Units noted droplids rough in ok cover
|
Electrical Rough-In | 4/9/2019 | 4/10/2019 | 4/10/2019 | A | PASS |
Rock A. Hudson
|
|
|
3RD , 4TH , 5TH floor trash and comm rm. , 3RD Bath rm. and 306 , 307 , 312 drop ceilings Phone #: ###-#### Inspection requested via web by Tom Betty Items noted adding fireplaces in units noted and level 2 planters wall pour in front of units 201, 202, 203 rough in ok cover
|
Electrical Rough-In | 4/1/2019 | 4/2/2019 | 4/2/2019 | A | PASS |
Mark Moncarr
|
|
|
Units 206 , 207 , 209 ,212 , 309 , 311 , 313 , 314 , 315 all drop ceilings Call John Phone #: ###-#### Inspection requested via web by Tom Betty Ok cover ceilings for units listed. Get some tools on Betty!
|
Electrical Rough-In | 3/14/2019 | 3/15/2019 | 3/15/2019 | A | PASS |
Rock A. Hudson
|
|
|
Unit 406 and drop ceilings units 211 , 212 , 213 , 214 and 215. Call John
Phone #: ###-#### Inspection requested via web by Tom Betty 406 and hardlids noted rough in ok cover
|
Electrical Rough-In | 3/11/2019 | 3/12/2019 | 3/12/2019 | A | PART |
Rock A. Hudson
|
|
|
Units 406 , 507 , 509 , 511 , 512 , 513 , 514 , 515 , North stairs #2 and South stairs #1 Call John Phone #: ###-#### Inspection requested via web by Tom Betty 406 must remove insulation incuding foam seal. rest noted rough in ok cover
|
Electrical Rough-In | 2/18/2019 | 2/19/2019 | 2/19/2019 | A | PASS |
Rock A. Hudson
|
|
|
Units 411 , 412 , 413 , 414 , 415 Call John Phone #: ###-#### Inspection requested via web by Tom Betty Units noted and 407, 409 rough in ok cover
|
Permanent Service | 2/15/2019 | 2/15/2019 | 2/15/2019 | A | PASS |
Rock A. Hudson
|
|
|
Main service Call John Phone #: ###-#### Inspection requested via web by Tom Betty House, tenant, and firepump services p/s u/g n ok
|
Electrical Rough-In | 2/12/2019 | 2/12/2019 | 2/12/2019 | A | PASS |
Rock A. Hudson
|
|
|
512 and 514 porches only Call John Phone #: ###-#### Inspection requested via web by Tom Betty Porches noted rough in ok cover
|
Electrical Rough-In | 2/7/2019 | 2/8/2019 | 2/8/2019 | A | PASS |
Rock A. Hudson
|
|
|
Units 306 , 307 , 309 Call John Phone #: ###-#### Inspection requested via web by Tom Betty Need to sign off inspections on print located on each floor. Areas noted rough in ok cover
|
Electrical Rough-In | 1/31/2019 | 2/1/2019 | 2/1/2019 | A | PASS |
Rock A. Hudson
|
|
|
Units 206 , 207 , 209 Phone #: ###-#### Inspection requested via web by Tom Betty Rooms as noted rough in ok cover
|
Electrical Rough-In | 1/29/2019 | 1/29/2019 | 1/29/2019 | A | PASS |
Rock A. Hudson
|
|
|
Units 311 , 312 , 313 , 314 , 315 Call John Phone #: ###-#### Inspection requested via web by Tom Betty Units foam sealed prior to inspection, informed next all will be removed before inspection will proceed as per BCC 4-05-23 unlawful to cover or conceal in any way wiring or cables. Rooms noted rough in ok cover
|
Electrical Rough-In | 1/23/2019 | 1/24/2019 | 1/24/2019 | A | PASS |
Rock A. Hudson
|
|
|
Drop ceilings unit 201 , 202 , 203 Call John Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted rough in ok cover
|
Electrical Rough-In | 1/15/2019 | 1/16/2019 | 1/16/2019 | A | PASS |
Rock A. Hudson
|
|
|
Units 211 , 212 , 213 , 214 , 215 and partials for patio cover units 312 , 314 , 412 , 414 Phone #: ###-#### Inspection requested via web by Tom Betty Patios only on 312, 314, 412, 414 and full units on other noted rough in ok cover.
|
Electrical Rough-In | 11/28/2018 | 11/28/2018 | 11/28/2018 | P | PART |
Rock A. Hudson
|
|
|
Discussed amount of water present on upper floors after rain over night. Contractor has recommended not pulling NM cable until dry sheeting done. Garage 1 side rough in ok cover only.
|
Electrical Rough-In | 11/28/2018 | 11/28/2018 | 11/28/2018 | A | NH |
Rock A. Hudson
|
|
|
Parking Garage one side sheet rock Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty No answer from contact. Must recall when available
|
Electrical Rough-In | 11/27/2018 | 11/27/2018 | 11/27/2018 | A | PASS |
Rock A. Hudson
|
|
|
Units 201 , 202 , 203 Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted roof dry sheeted with no noticable water in units. Rough in ok cover
|
Conference | 11/27/2018 | 11/27/2018 | 11/27/2018 | P | DONE |
Rock A. Hudson
|
|
|
Units 201 , 202 , 203 Phone #: ###-#### Inspection requested via web by Tom Betty Discussed NEC 210.52 general receptacles- required on back of kitchen bar area where faces rooms noted, living, dining, entry, ect. Discussed NEC 334.12- Uses not permitted for installing NM cable. NM cable shall not be installed in a damp or wet location. If NM cable becomes wet due to weather it shall be removed and replaced. Standing water found on level 2 of west building in several units. Will check often.
|
Electrical Rough-In | 9/26/2018 | 9/26/2018 | 9/26/2018 | A | PASS |
Daryl DeGrange
|
|
|
Sprinkler riser room Phone #: ###-#### Inspection requested via web by Tom Betty Rough-in ok to one side Riser Room
|
Electrical Rough-In | 9/10/2018 | 9/10/2018 | 9/10/2018 | A | PASS |
James Ady
|
|
|
Electrical and fire riser room Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Fire riser room and main electrical rooms, interior one side only.
|
Electrical Rough-In | 7/18/2018 | 7/18/2018 | 7/18/2018 | A | PASS |
Rock A. Hudson
|
|
|
P.T. deck inspection Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Complete PT deck rough in ok cover
|
Electrical Rough-In | 6/26/2018 | 6/26/2018 | 6/26/2018 | A | PASS |
Rock A. Hudson
|
|
|
Underground SE corner of building Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Service entrance conduits from tranformer to building rough in ok cover
|
Electrical Rough-In | 6/18/2018 | 6/18/2018 | 6/18/2018 | A | PASS |
Rock A. Hudson
|
|
|
Under ground west gridline 4 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Area noted rough in ok cover
|
Electrical Rough-In | 6/12/2018 | 6/12/2018 | 6/12/2018 | A | PASS |
Rock A. Hudson
|
|
|
Ground work N.E.corner of building Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Underground east side to grid line 4 rough in ok cover
|
Electrical Rough-In | 6/7/2018 | 6/7/2018 | 6/7/2018 | A | PASS |
Rock A. Hudson
|
|
|
Under ground south end of building park by job trailers call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Service entrance and branch conduits out of south electrical room underground rough in ok cover
|
Electrical Rough-In | 5/23/2018 | 5/23/2018 | 5/23/2018 | A | PASS |
Rock A. Hudson
|
|
|
Ufer Inspection Contact Craig Timmons Thank you Phone #: ###-#### Inspection requested via web by Tom Betty 20 or more #4 copper bare conductor tied to rebar must be encased in 2" or more. Must elevate above ground. Will verify when rebar complete. Rough in ok cover
|
Issue PAID IN FULL permit | | | 5/23/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/23/2018 | | DONE |
|
|
|
This permit was created on the web by Tom Betty
|
First Notice | 10/7/2019 | 10/7/2019 | | | |
Rock A. Hudson
|
|
|
|
First Notice | 9/17/2019 | 9/17/2019 | | | |
Rock A. Hudson
|
|
|
|