General Inspection | 12/14/2018 | 12/14/2018 | 12/14/2018 | | CANC |
Michael Zawacki
|
|
|
|
DOC - Permit Finaled | 12/14/2018 | 12/14/2018 | 12/14/2018 | P | PASS |
Michael Zawacki
|
|
|
|
General Inspection | 11/27/2018 | 11/29/2018 | 11/29/2018 | P | PASS |
Michael Zawacki
|
|
|
All work complete. Sent message to Kyle to pull inlet protection so permit can be closed.
|
General Inspection | 11/22/2018 | 11/22/2018 | 11/27/2018 | | CANC |
Andy J. Long
|
|
|
rescheduled
|
General Inspection | 11/7/2018 | 11/7/2018 | 11/8/2018 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 10/23/2018 | 10/23/2018 | 10/23/2018 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 10/8/2018 | 10/8/2018 | 10/9/2018 | | PASS |
Andy J. Long
|
|
|
WIP on NW corner units. No trackout or muddy runoff occuring during rain event.
|
General Inspection | 9/21/2018 | 9/21/2018 | 9/21/2018 | P | PEND |
Michael Zawacki
|
|
|
Site contained. Left message with Kyle to remove or repair silt fence.
|
General Inspection | 9/13/2018 | 9/13/2018 | 9/13/2018 | | PASS |
Michael Zawacki
|
|
|
Most concrete work completed. Silt fence along Warm Springs is collapsed and needs to be removed. Landscape material now staged on site.
|
General Inspection | 8/29/2018 | 8/29/2018 | 8/31/2018 | | PASS |
Andy J. Long
|
|
|
Final phase in NW corner near completion. Driveway has been poured, washout pan in Barber Crossing was utilized. Will need to check that area for cleaning for any spills. See ESC17-00018. No corrections at this time.
|
General Inspection | 8/14/2018 | 8/14/2018 | 8/14/2018 | | PASS |
Michael Zawacki
|
|
|
Work on last section. All mess and debris is contained to work area.
|
General Inspection | 7/30/2018 | 7/30/2018 | 7/30/2018 | | PART |
Michael Zawacki
|
|
|
Silt fence on north side has fallen and can be removed, no longer serving any purpose. Trusses are being stored on sidewalk. Lots of stucco waste on homesites.
|
General Inspection | 7/13/2018 | 7/13/2018 | 7/13/2018 | | PASS |
Michael Zawacki
|
|
|
WIP on last phase. Site is clean, contractors responsible for their own areas.
|
General Inspection | 6/28/2018 | 6/28/2018 | 6/28/2018 | | PASS |
Michael Zawacki
|
|
|
Some of the perimeter silt fence has collapsed, acting more as fence than containment. Idaho power is currently on site. Site is mostly clean, some bottles and trash stuck on fence. No dust or trackout.
|
General Inspection | 6/13/2018 | 6/13/2018 | 6/14/2018 | | PASS |
Michael Zawacki
|
|
|
Area is prepped for homes and stable. No building has begun.
|
General Inspection | 5/29/2018 | 5/29/2018 | 5/30/2018 | | PASS |
Michael Zawacki
|
|
|
WIP on final phase. Landscapers on site on section, have gotten some dirt on sidewalk. All working sites contained and clean.
|
General Inspection | 5/14/2018 | 5/14/2018 | 5/14/2018 | | PASS |
Michael Zawacki
|
|
|
New phase on Pheasant Tail. Rest of site nearly finished and clean.
|
General Inspection | 4/27/2018 | 4/27/2018 | 4/27/2018 | | PASS |
Andy J. Long
|
|
|
WIP. New silt installed around last block of homes now in construction. BMPs installed in sub, RP on duty.
|
General Inspection | 4/12/2018 | 4/12/2018 | 4/12/2018 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 3/27/2018 | 3/28/2018 | 4/2/2018 | A | PASS |
Andy J. Long
|
|
|
trash etc
Trash in drain area and wooded area at NE corner of project has been picked up.
|
General Inspection | 3/20/2018 | 3/23/2018 | 3/27/2018 | P | PEND |
Andy J. Long
|
|
|
|
General Inspection | 3/15/2018 | 3/15/2018 | 3/20/2018 | P | PART |
Andy J. Long
|
|
|
No trackout or discharges in subdivision. Storm drains have sediment protection. Concrete washout facility provided for this round of foundations.
Correction request to be completed this week: - pick up trash to the west of project in vegetated and woody natural area between project and old Eckert Road.
RP Kyle said it will be picked up this week. Follow up inspection scheduled.
|
General Inspection | 3/1/2018 | 3/1/2018 | 3/2/2018 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 2/14/2018 | 2/14/2018 | 2/15/2018 | | PASS |
Michael Zawacki
|
|
|
WIP. Some light trackout.
|
General Inspection | 1/30/2018 | 1/30/2018 | 1/30/2018 | | PASS |
Andy J. Long
|
|
|
BMPs installed. RP notified that Greenbelt to be swept thoroughly once it is no longer needed for construction access.
|
General Inspection | 1/15/2018 | 1/15/2018 | 1/16/2018 | | PASS |
Andy J. Long
|
|
|
No trackout from active areas. Workers parking on streets. Subdivision storm drains have sediment protection installed. Will need to monitor silt fence along Greenbelt Path along Warm Springs, it has been opened up for site access.
|
General Inspection | 12/29/2017 | 12/29/2017 | 12/29/2017 | | CANC |
Andy J. Long
|
|
|
|
Random Inspection | 12/14/2017 | 12/14/2017 | 12/14/2017 | P | PASS |
Michael Zawacki
|
|
|
Rock Placing Company will be raising the rear retaining wall, began to stage material. Silt fence along rear was buried. Very little dirt leaving site.
|
General Inspection | 12/1/2017 | 12/1/2017 | 12/1/2017 | | PEND |
Michael Zawacki
|
|
|
Some tracking onto sidewalks. Area around Pheasent Tail and Warm Springs needs perimeter control. Landscapers are doing perimeter along Eckert.
|
BMP Violation | 11/15/2017 | 11/16/2017 | 11/20/2017 | P | PASS |
Michael Zawacki
|
|
|
check for construction entrance and sweep up. Entrance installed on both sides. Majority of trackout has been swept up. Some dirt running down gutters during rain event.
|
Tracking Control | 11/14/2017 | 11/15/2017 | 11/15/2017 | A | PEND |
Michael Zawacki
|
|
|
Walked through site with RP. Discussed issues and will check back to see if completed.
|
General Inspection | 11/14/2017 | 11/14/2017 | 11/14/2017 | | FAIL |
Andy J. Long
|
|
|
Trackout from concrete washout area on Caddis and surrounding streets.
Corrections needed: - clean up trackout on streets - provide rock construction entrance access to washout
RP with Hunter Homes said clean up is in progress, rock will be ordered. Tracking control followup scheduled.
|
General Inspection | 10/30/2017 | 10/30/2017 | 10/31/2017 | | PEND |
Michael Zawacki
|
|
|
Remove, repair, or replace silt fence along Eckert. Lots of dirt on sidewalks. Silt fence along Warm Springs is load bearing and failing. Gravel was dumped on sidewalk next to unprotected inlet. Talked to RP and said he'd get it taken care off.
|
General Inspection | 10/13/2017 | 10/13/2017 | 10/13/2017 | | CANC |
Michael Zawacki
|
|
|
|
General Inspection | 9/28/2017 | 9/28/2017 | 9/28/2017 | P | PASS |
Andy J. Long
|
|
|
Harris Crossing is in its final phases. Excavation for units at north end of sub along Greenbelt will start next week. Framing and interior work occuring on Caddis & Mill Station. SWPPP sign posted here.
Trash contained, no trackout, fugitive dust or other issues observed. Storm drains still have sediment bags installed. No corrections at this time.
|
General Inspection | 9/18/2017 | 9/18/2017 | 9/19/2017 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 9/1/2017 | 9/1/2017 | 9/5/2017 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 8/17/2017 | 8/17/2017 | 8/18/2017 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 8/2/2017 | 8/2/2017 | 8/2/2017 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 7/11/2017 | 7/18/2017 | 7/17/2017 | A | PASS |
Melissa Jannusch
|
|
|
Pile has been moved back from silt fence. Some dirt on sidewalk on Pheasant tail way that needs to be swept up. No other ESC issues.
|
General Inspection | 7/11/2017 | 7/11/2017 | 7/11/2017 | | PART |
Melissa Jannusch
|
|
|
Silt fence is being overwhelmed by backfill pile and near its breaking point. Called RP Kyle and let him know. WIP on townhomes.
|
General Inspection | 6/26/2017 | 6/26/2017 | 6/27/2017 | | PASS |
Melissa Jannusch
|
|
|
WIP on SFHs. Some areas still not under construction yet. Small amount of trackout. Concrete washouts okay. Trash contained. No corrections.
|
General Inspection | 6/6/2017 | 6/9/2017 | 6/9/2017 | A | PART |
Melissa Jannusch
|
|
|
Okay to start homes on Caddis way. Silt fence installed along perimeter. Needs to improve both entrances to prevent trackout.
Trash containment has been provided on pheasant tail way and most trash has been cleaned up. There is still some windblown trash in natural area that needs to be cleaned.
|
General Inspection | 6/5/2017 | 6/5/2017 | 6/6/2017 | P | PART |
Melissa Jannusch
|
|
|
ECB have been staked down. No other ESC isues observed.
|
General Inspection | 5/31/2017 | 5/31/2017 | 5/31/2017 | | CANC |
Melissa Jannusch
|
|
|
|
General Inspection | 5/16/2017 | 5/16/2017 | 5/16/2017 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 5/1/2017 | 5/1/2017 | 5/1/2017 | | PASS |
Andy J. Long
|
|
|
|
General Inspection | 4/14/2017 | 4/14/2017 | 4/14/2017 | P | PASS |
Melissa Jannusch
|
|
|
No trackout. Gravel has been added to entrance/exit. No WIP at time of inspection.
|
General Inspection | 4/13/2017 | 4/13/2017 | 4/13/2017 | | PASS |
Melissa Jannusch
|
|
|
WIP on townhomes. Trackout has been cleaned. No new trackout. No windblown trash. Project ok
|
General Inspection | 3/29/2017 | 3/29/2017 | 3/29/2017 | | PASS |
Melissa Jannusch
|
|
|
WIP on townhomes. Subdivision BMPs are okay. Trackout has been cleaned. No corrections.
|
General Inspection | 3/14/2017 | 3/14/2017 | 3/14/2017 | | PASS |
Melissa Jannusch
|
|
|
Silt fence is installed. Spoke with RP Kyle on site this morning construction entrance will be installed this week. Rest of subdivision has some slight trackout. Subdivision okay.
|
General Inspection | 2/27/2017 | 2/27/2017 | 2/27/2017 | | PASS |
Andy J. Long
|
|
|
WIP on homes within central area of subdivsion. No trackout from shared driveway accesses observed. New construction enrance rock installed for concrete washout facility. Approved.
|
Tracking Control | 2/10/2017 | 2/10/2017 | 2/10/2017 | A | PASS |
Melissa Jannusch
|
|
|
Track out has been cleaned, construction entrance has been made, and concrete washouts are on site.
|
General Inspection | 2/6/2017 | 2/6/2017 | 2/8/2017 | | PART |
Melissa Jannusch
|
|
|
Track out from site onto mill station and caddis right up to Eckert. Correction request: Called RP. Heplans to clean and sweep. Suggested improving construction entrance.
|
General Inspection | 1/20/2017 | 1/20/2017 | 1/27/2017 | | CANC |
Melissa Jannusch
|
|
|
Road closed due to landslide and adverse winter conditions
|
General Inspection | 1/5/2017 | 1/5/2017 | 1/10/2017 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 12/21/2016 | 12/21/2016 | 12/29/2016 | | PASS |
Andy J. Long
|
|
|
WIP in central area of Harris Crossing. BMPs installed. Site snow covered. No trackout, muddy access areas or other issues observed.
|
General Inspection | 12/6/2016 | 12/6/2016 | 12/7/2016 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 11/21/2016 | 11/21/2016 | 11/21/2016 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 11/4/2016 | 11/4/2016 | 11/4/2016 | | PASS |
Andy J. Long
|
|
|
WIP on new excavation in central area. Stockpiles currently in process of removal/relocation. Some trackout within in subdivision.
Concrete washout facility with two containment bins provided. Inlets has sediment protection.
Approved
|
General Inspection | 10/20/2016 | 10/20/2016 | 10/20/2016 | | PASS |
Andy J. Long
|
|
|
WIP on central area townhomes at Harris Crossing. BMPs installed including concrete washout container, adequate trash containment for multiple units, DI protection, silt fence along downslope end of site near power lines and Eckart, and periodic street sweeping.
No trackout to roads, no sediment or mud in gutters.
Correction request/notification concrete washout is over 50% full and a service call should be made
|
General Inspection | 10/5/2016 | 10/5/2016 | 10/5/2016 | | PASS |
Andy J. Long
|
|
|
WIP on central SFHs. BMPS installed. Trash and materials are contained. A new washout facility has been provided as requested since the old washout is now full. This washout is used for HH projects in DHE as well.
No trackout, fugitive dust, or other issues. WIP. Approved.
|
General Inspection | 9/20/2016 | 9/20/2016 | 9/21/2016 | | PASS |
Andy J. Long
|
|
|
WIP on units within central subdivision area. Framing work only. No trackout, fugitive dust or windblown trash issues. The south end of project not yet landscaped or vegetated had temporary fiber tacifier applied and silt fence installed at the bottom of the slightly sloping area.
Concrete washout is in good condtion but is near capacity. Currently being utilized for Hunter Homes SFHs in Dallas Harris Estates.
Correction request to Wes with HH to dig new washout facility.
|
General Inspection | 9/5/2016 | 9/5/2016 | 9/6/2016 | | PASS |
Andy J. Long
|
|
|
WIP on the central portion of Harris Crossing subdivision. BMPs installed. Trash containers provided, lined washout and inlet protection. No violations.
|
General Inspection | 8/19/2016 | 8/19/2016 | 8/19/2016 | | PASS |
Evan Jenkins
|
|
|
|
General Inspection | 8/4/2016 | 8/4/2016 | 8/5/2016 | | PASS |
Andy J. Long
|
|
|
WIP on townhomes on the east side of Pheasant Tail. Individual SFH permits issued, sites are clean temp BMPs installed including washout and storm drain protection. All construction on the south Caddis culdesac is complete and landscaped - individual ESC permit for those have been closed out.
|
General Inspection | 7/20/2016 | 7/20/2016 | 7/20/2016 | | PASS |
Andy J. Long
|
|
|
|
General Inspection | 7/5/2016 | 7/5/2016 | 7/5/2016 | | PASS |
Evan Jenkins
|
|
|
no issues observed at time of inspection
|
General Inspection | 6/20/2016 | 6/20/2016 | 6/20/2016 | | PASS |
Andy J. Long
|
|
|
Subdivision BMPs installed. WIP on SFHs. No earthwork at this time. No corrections needed.
|
General Inspection | 6/3/2016 | 6/3/2016 | 6/3/2016 | | PASS |
Andy J. Long
|
|
|
SFHs already framed are being finished. No active concrete work. Sites are clean, no wind blown trash or dust issues, no trackout, no discharges. Storm drains have inlet sediment filter bags. No corrections needed at this time.
|
General Inspection | 5/19/2016 | 5/19/2016 | 5/19/2016 | | PASS |
Andy J. Long
|
|
|
No earthwork occuring at this time. Crews working on interiors on track of home on east side of Caddis. BMPs installed, no trackout or turbid discharges off site.
|
General Inspection | 5/4/2016 | 5/4/2016 | 5/4/2016 | | PASS |
Andy J. Long
|
|
|
Subdivision BMPs installed. Individual SFHs have permit signs posted and are in compliance. No corrections issued.
|
General Inspection | 4/19/2016 | 4/19/2016 | 4/19/2016 | | PASS |
Andy J. Long
|
|
|
WIP on homes on the east side of Caddis and south of Mill Station. No trackout, loose sediment, or other debris/materials on roadways & gutters. DIs have sediment filter bags that have been maintained regularly. No concrete work occuring at this time, only framing. Will need to re-line the concrete washout pits when new foundations are to begin.
Subdivision is clean, no corrections at this time.
|
General Inspection | 4/4/2016 | 4/4/2016 | 4/5/2016 | | PART |
Andy J. Long
|
|
|
WIP on frames on Caddis Street. Streets are clean and free of trackout. DIs have sediment filter bags installed. No windblown trash issues observed.
Correction request: - install new lined concrete washout prior to more concrete work or site preparation approval; remove and dispose of old washout materials. - prohibit parking on open parcel if muddy (ie: train employees to avoid trackout)
|
General Inspection | 3/18/2016 | 3/18/2016 | 3/18/2016 | | PASS |
Evan Jenkins
|
|
|
No issues observed at time of inspection
|
General Inspection | 3/3/2016 | 3/3/2016 | 3/3/2016 | | PASS |
Andy J. Long
|
|
|
|
General Inspection | 2/17/2016 | 2/17/2016 | 2/17/2016 | | PASS |
Eric Strole
|
|
|
Looks good.
|
General Inspection | 2/2/2016 | 2/2/2016 | 2/3/2016 | | PASS |
Andy J. Long
|
|
|
WIP on homes in Harris Crossing. Street sweeper doing routine cleaning at time of inspection. Concrete washout is lined and designated, no leaks or spills.
Individual houses covered by seperate ESC permits. Need to make sure alley way DIs have inlet protection. Approved.
|
General Inspection | 1/18/2016 | 1/18/2016 | 1/19/2016 | | PASS |
Evan Jenkins
|
|
|
|
General Inspection | 1/1/2016 | 1/1/2016 | 1/4/2016 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 12/17/2015 | 12/17/2015 | 12/17/2015 | | PASS |
Andy J. Long
|
|
|
WIP on SFHs. No violations observed. No earthwork or excavation at this time. BMPs installed.
|
General Inspection | 12/2/2015 | 12/2/2015 | 12/2/2015 | | PASS |
Andy J. Long
|
|
|
WIP of SFH townhomes in Harris Crossing. All DIs have inlet protection, silt fence containing sediment from active projects on east side of Caddis is effective. Some trackout through subdivision will be addressed with the regular scheduled sweeping. No trackout off site, no wind blown trash issues. Designated lined concrete washout installed.
No corrections at this time. Will suggest installation of a wattle on the west boundary of the central open area. Ground has not been tacified but has some vegetation.
|
General Inspection | 11/16/2015 | 11/17/2015 | 11/18/2015 | A | PASS |
Andy J. Long
|
|
|
Lucky Harris 13, now Harris Crossing has active SFH construction in progress by Hunter Homes. SFHs within subdivision are permitted seperately.
Site is in good condition with no erosion or areas of sediment runoff. Perimeter is contained by combination of landscaping, preservation of existing vegetation, and installed of silt fence. A new section of silt fence has been installed to protect the Greenbelt path way from work on the east side of Caddis.
Lined concrete washout provided, trash containers are onsite, and storm drains have protection.
No violations, no correction requests at this time.
|
General Inspection | 11/16/2015 | 11/16/2015 | 11/16/2015 | | CANC |
Andy J. Long
|
|
|
rescheduled for 11/17
|
General Inspection | 10/30/2015 | 10/30/2015 | 10/30/2015 | | PASS |
Andy J. Long
|
|
|
Lucky Harris 13/Harris Crossing. New set of SFHs in progress at south end of sub. No trackout or discharges from site. No windblown litter due to trash containers. DIs protected, limits of disturbance respected with vegetative perimeter in addition to some sediment control BMPs. No corrections.
|
General Inspection | 10/15/2015 | 10/15/2015 | 10/15/2015 | | PASS |
Andy J. Long
|
|
|
WIP on homes in Harris Crossing. No sedment leaving site at perimeters. No trackout to streets, DIs protected and designated washouts being utilized. No fugitive ust observed. Approved.
|
General Inspection | 9/30/2015 | 9/30/2015 | 9/30/2015 | | PASS |
Evan Jenkins
|
|
|
No ESC Violations observed at time of inspection. WIP on SFD's
|
General Inspection | 9/15/2015 | 9/15/2015 | 9/15/2015 | | PASS |
Andy J. Long
|
|
|
WIP on homes at sound end of project. BMPs include DI bags, designated washout, and restricted access to open areas to prevent tracking. No discharges, dust, or other violations observed. No corrections at this time.
|
General Inspection | 8/31/2015 | 8/31/2015 | 8/31/2015 | | PART |
Andy J. Long
|
|
|
WIP at south end of Lucky Harris sub. Trash contained, clearing limits are being respected and perimeter BMPs installed. DI bags installed on all inlet. Projects have permit signs posted.
1 correction: - need to allow current washout to dry out and haul away. Install new washout for next round of homes. 5 new ones were just poured and washout was utilized..
|
General Inspection | 8/14/2015 | 8/14/2015 | 8/14/2015 | | PART |
Andy J. Long
|
|
|
Lucky Harris 13/Harris Crossing subdivision has two units in progress at the south end of culdesac. Concrete washout that was formerly in this spot has been moved across the culdesac.
First set of homes on Pheasant Tail are all complete and landscaped. Individual permits finaled. No fugitive dust, trackout, windblown trash or other issues.
Correction:
-Secure lining of concrete washout pit and post a sign that says designated washout.
|
General Inspection | 7/30/2015 | 7/30/2015 | 7/30/2015 | | PASS |
Andy J. Long
|
|
|
No new SFHs being built, no trackout, discharges or other issues. Will start next round of homes in late August or September
|
General Inspection | 7/15/2015 | 7/15/2015 | 7/15/2015 | | PASS |
Andy J. Long
|
|
|
|
Random Inspection | 6/30/2015 | 6/30/2015 | 6/30/2015 | A | PASS |
Andy J. Long
|
|
|
No construction activity currently in Harris Crossing - first round of townhomes are completed, the 6 southern most homes still have a few finishing touches and patio landscaping to be completed. Finaled out ESC permits for all townhomes on Pheasant Tail between 3###-####.
No corrections at this time. No violations, dust, trash issues, or discharges observed.
|
General Inspection | 6/18/2015 | 6/18/2015 | 6/18/2015 | | PART |
Andy J. Long
|
|
|
Need to replace concrete washout. All other BMPs are in good condition (DI bags, waste management, trackout control). First round of homes on Pheasant Tail are being landscaped.
Correction requested to Hunter Homes for concrete washout maintenance.
|
General Inspection | 6/3/2015 | 6/3/2015 | 6/3/2015 | | PASS |
Evan Jenkins
|
|
|
|
General Inspection | 5/18/2015 | 5/19/2015 | 5/19/2015 | A | PASS |
Andy J. Long
|
|
|
Streets and gutters free of loose sediment or trackout from home construction. Lined concrete washout has been maintained and is ready for next set of foundations at Harris Crossing. All DIs have filter bags, south edge of site has been hydroseeded and grass is starting to grow. No corrections at this time.
|
General Inspection | 5/18/2015 | 5/18/2015 | 5/18/2015 | | CANC |
Andy J. Long
|
|
|
rescheduled
|
General Inspection | 5/1/2015 | 5/1/2015 | 5/1/2015 | | PASS |
Andy J. Long
|
|
|
15 homes are near completion at Lucky Harris/Harris Crossing. Lined concrete washout facility has been well maintained and utilized. RP Chad informed that Ground FX will be handling ESC issues for Hunter Homes, as well as Hunter Homes SFH RP Ausitn.
Trash is contained, no trackout or discharges. Perimeter BMPs and inlet protection in good condition. Disturbed area at sound of site has been hydroseed for stabilization.
Approved.
|
General Inspection | 4/16/2015 | 4/16/2015 | 4/16/2015 | | PART |
Andy J. Long
|
|
|
Homes in progress within Harris Crossing. No trackout, discharges, or fugitive dust. No sediment leaving development area and onsite stormdrains are protected.
Some of the perimeter BMPs need maintenance. Several sections of damaged silt fence need removal or repair. Empty or remove DI bags no longer needed. Requested to RP Chad send ESC crew to fix this week or next. No active erosion or sediment control issues.
|
General Inspection | 4/1/2015 | 4/1/2015 | 4/1/2015 | | PASS |
Andy J. Long
|
|
|
Lucky Harris/Harris Crossing sub has townhomes in progress. Trash and materials are contained, perimeter BMPs are installed, DI protection provided, and employees are staying off open areas to prevent disturbance/trackout. Designated and lined washout is being utilized and has remaining capacity. Landscaping crews on site working to vegetate/stabilize subdivision perimter.
No corrections at this time.
|
General Inspection | 3/17/2015 | 3/17/2015 | 3/17/2015 | | PART |
Andy J. Long
|
|
|
Lucky Harris 13 subdivision streets and gutters are clean and stormdrain inlets have sediment capture bags. Work on homes is now underway and work is staying within confines of area of disturbance and perimeter BMPs are in place.
Corrections: 1. Repair section of downed silt fence 2. Install inlet protection on the stormdrains on the shared driveways (or provide alternative BMP)
|
General Inspection | 3/2/2015 | 3/2/2015 | 3/2/2015 | | PASS |
Evan Jenkins
|
|
|
WIP: minimal trackout occuring from individual SFH projects. No other issues at this time
|
General Inspection | 2/13/2015 | 2/13/2015 | 2/13/2015 | | PASS |
Evan Jenkins
|
|
|
Some standing water on lots, but no discharge occuring at time of inspection
|
General Inspection | 1/29/2015 | 1/29/2015 | 1/29/2015 | | PASS |
Andy J. Long
|
|
|
Lucky Harris 13 subdivision now has Hunter Homes crews onsite working on the townhome "pods" - 6 units with a single access driveway off Pheasant Tail. There is some trackout on streets within the subdivision due to muddy conditions, but very little on Eckart and Warm Springs. Subdivsion DI's have filter bag inserts installed. No discharges offsite and perimeter BMPS are still installed. Lined concrete washout is at the south end of the project and is in good condtion and being used as directed.
|
Tracking Control | 1/14/2015 | 1/14/2015 | 1/14/2015 | P | PART |
Andy J. Long
|
|
|
No discharges offsite and no trackout beyond subdivision.
The streets within Lucky Harris 13 has lots of trackout from heavy vehicle unloading and no stabilized entrances in higher use areas.
Corrections: 1. Clean up loose sediment and dirt/ mud clods as conditions allow. 2. Designate staging area for landscaping materials and other sub developement work. 3. Train contractors to prevent trackout as much as possible.
Hunter Homes needs to come up with plan to mitigate this trackout to prevent sediment from leaving site and damaging drainage system.
|
General Inspection | 1/7/2015 | 1/7/2015 | 1/7/2015 | | PASS |
Andy J. Long
|
|
|
Lucky Harris 13 has all infrastructure and utilities installed. Some common area landscaping remains. Currently 6 new SFHs by Hunter Homes are being built.
Streets will need to be swept at least 1x per week. DI bags installed, lined washout for projects located at south culdesac on Caddis St..
|
Complaint Inspection | 12/23/2014 | 12/23/2014 | 12/23/2014 | P | PEND |
Andy J. Long
|
|
|
Section of Greenbelt through subdivision is submerged. This is due to the fact rain came during landscaping operations and prior to installation of area drains for that area. Hunter Homes RP Chad stated landscaping will be finished once conditions allow and that the water will be removed via pump and hose and land applied or directed to Lucky Harris sub private onsite drainage system.
No discharges offsite or trackout off site observed, some within interior of sub due to ongoing/interupted landscaping.
Will continue to monitor. PW coming to inspect drainage design.
|
General Inspection | 12/17/2014 | 12/17/2014 | 12/17/2014 | | PART |
Andy J. Long
|
|
|
Perimeter BMPs installed and no trackout off site onto Warm Springs or Eckart.
Crews onsite grading parcels, installing irrigation, and other parcel preparations and causing trackout within neighborhood streets. This will need to be cleaned this week. DI bags in sub have inlet protection.
|
General Inspection | 12/2/2014 | 12/2/2014 | 12/2/2014 | | PASS |
Andy J. Long
|
|
|
Lucky Harris 13 streets, curbs and sidewalks have been installed. Stockpile and disturbed earth at south end of site has sediment perimeter BMPs installed. The new drop inlets within the subdivision have filter bag protection.
Some survey and electrical utility crews on site, but no major activity. No corrections at this time, site looks good considering the recent precipitation. Approved.
|
General Inspection | 11/17/2014 | 11/17/2014 | 11/17/2014 | | PASS |
Andy J. Long
|
|
|
Some minor work ongoing at Lucky Harris. No trackout, no issues from weekend snowmelt, most of site is still frozen. We continue to monitor as conditions warm up and more work resumes.
|
General Inspection | 10/31/2014 | 10/31/2014 | 10/31/2014 | | PASS |
Evan Jenkins
|
|
|
Inspection performed earlier today. Site is in good shape with no ESC issues at this time
|
General Inspection | 10/16/2014 | 10/16/2014 | 10/16/2014 | | PASS |
Andy J. Long
|
|
|
No dust, trackout, or signinficant sediment accumulation in gutters along Eckart Road for the Lucky 13 Project. In process of installation of sewer/utilities and grading for roadways. Silt fence on southwest boundary protecting drainage/Idaho Power area is installed and has vegetative buffer.
No corrections at this time.
|
General Inspection | 10/1/2014 | 10/1/2014 | 10/1/2014 | P | PASS |
Andy J. Long
|
|
|
Follow up inspection:
Surrounding gutters and DI at Eckart and Arrow Junction has been cleaned and the filter bag emptied and reinstalled.
No new trackout from Ranch Market construction entrance.
|
Tracking Control | 9/30/2014 | 9/30/2014 | 9/30/2014 | P | PASS |
Andy J. Long
|
|
|
2 corrections at Lucky Harris sub development:
1. Sweep, clean, and maintan DI bag at corner Eckart and Arrow Junction.
2. Restrict construction vehicle access to the designated south entrance (not Ranch Market access)
RP Chad stated that Syman Co. will be cleaning inlet today or tomorrow AM and that he will coordinate with Ranch Market builders to come to agreement on their construction entrance.
Will continue to monitor this week.
|
General Inspection | 9/24/2014 | 9/24/2014 | 9/24/2014 | | PASS |
Andy J. Long
|
|
|
Lucky Harris 13 is in progress as well as the Eckart Greenbelt path (ESC14-00885) to the south of site. No trackout and water truck on site. Some dust related to construction vehicle movement, but not being stirred up by wind and crossing project boundaries.
|
General Inspection | 9/9/2014 | 9/9/2014 | 9/9/2014 | | PASS |
Andy J. Long
|
|
|
Lucky Harris 13 in progress of installing sewer and utilities. Site has been in good condition since the previous trackout and sediment issues on Eckart and Arrow Junction was address. No new corrections at this time.
|
BMP Violation | 8/22/2014 | 8/22/2014 | 8/22/2014 | P | PEND |
Andy J. Long
|
|
|
Correction notice issued to sweep and shovel collected sediment and rocks from Lucky Harris at 11:30 AM. Scheduled onsite meeting with RP Chad Hamel at 1:30 PM.
Between the time of CN and meeting, Chad had Brown Construction laborers come and shovel the gutters and run their onsite sweeper (no vacuum). To follwo up Curtis Clean Sweep will be coming this afternoon with a vacuum for a deeper clean.
Beginning of next week Schmidt will turn over/scarify exisitng rock entrance which has filled in.
Response and corrective actions were prompt after initial requests this week were unfulfilled.
Will check conditions on Monday.
|
Tracking Control | 8/19/2014 | 8/19/2014 | 8/19/2014 | P | FAIL |
Andy J. Long
|
|
|
Follow on Lucky Harris sub corrections.
Wattle on Eckart was replaced and DI bag south of Arrow Junction Street was maintained.
Remaining corrections: 1. Street sweeping along Eckart and Arrow Junction. 2. DI bag on Arrow Junction (north side of street) is full and was not replaced.
|
Complaint Inspection | 8/18/2014 | 8/18/2014 | 8/18/2014 | A | FAIL |
Andy J. Long
|
|
|
3 corrections required to be completed end of day Tuesday 8/19:
1. Sweep and remove rocks, gravel, and sediment around the intersection of Eckart and Arrow Junction. 2. Empty and replace drop inlet sediment filter bags on all stormdrains around site. 3. Maintain wattles on Eckart south of construction entrance.
|
Tracking Control | 8/15/2014 | 8/15/2014 | 8/15/2014 | A | PASS |
Andy J. Long
|
|
|
Follow up inspection:
Road was swept as requested and street sweeper is now on site as well as water truck for dust suppression. No issues at time of inspection, will need to continue daily sweeping to keep rocks and gravel off road. Construction entrance has been restored.
|
General Inspection | 8/13/2014 | 8/13/2014 | 8/13/2014 | | PART |
Andy J. Long
|
|
|
Corrections required:
1. Increase use of water truck. Issued warning to RP Chad, the water truck was put in motion as I was leaving site.
2. Sweep east side of Eckart to remove rocks tracked out from construction entrance and sediment. Scoop up sediment trapped by wattle.
3. Refresh construction entrance with more rock, or turn over/scrape existing rock.
Corrections will be made before end of day per RP Chad. Will follow up tomorrow morning.
|
General Inspection | 7/29/2014 | 7/29/2014 | 7/29/2014 | | PASS |
Andy J. Long
|
|
|
Lucky Harris 13 in process of installing sewer and utility (contractor is Schmidt Construction) No dust or other issues. Working on connecting water lines on Eckert so they will need to sweep once complete. Remaining with limits of disturbance and silt fence perimeter is in good condition.
|
General Inspection | 7/11/2014 | 7/11/2014 | 7/11/2014 | | PASS |
Andy J. Long
|
|
|
No activity at time of inspection. No trackout to Eckart, permit posted, silt fence perimeter in good condition. Fill and grading is complete, remaining stockpile has vegetated. No dust observed.
|
General Inspection | 6/26/2014 | 6/26/2014 | 6/26/2014 | | PASS |
Andy J. Long
|
|
|
Lucky Harris 13 subdivision development project has permit posted, construction entrance, silt fence and inlet protection. No trackout or discharges observed.
Next inspection will check DI bags and Eckart for maintenance needs. Currently have remaining capacity.
|
General Inspection | 6/11/2014 | 6/11/2014 | 6/11/2014 | | PASS |
Andy J. Long
|
|
|
Lucky Harris subdivision development is currently in compliance. No trackout or significant sediment from site on Eckart. No dust issues observed or reported. Permit and SWPPP on site. The southwest border has proper perimeter controls and additonal stockpile control. Approved. No corrections at this time. Looks like they are near completion of the infill phase, raising the area elevation by 14'.
|
Random Inspection | 5/27/2014 | 5/27/2014 | 5/27/2014 | P | PASS |
Andy J. Long
|
|
|
No major dust or trackout issues at site. Doing a good job doing regular cleanup. The construction entrance will need more stabilized rock soon.
|
General Inspection | 5/14/2014 | 5/14/2014 | 5/14/2014 | | PART |
Andy J. Long
|
|
|
No sediment leaving site in form of fugitve dust - water truck is on site.
Some rock from construction entrance has been tracked out to Warm Springs. Will check tomorrow to see if daily sweeping corrects the issued, otherwise will put CN to clean streets and maintain construction entrance. Silt fence permiter in good condition.
|
General Inspection | 4/24/2014 | 4/24/2014 | 4/24/2014 | | PASS |
Andy J. Long
|
|
|
Construction entrance still in decent condition. No on or off hauling operations at the moment, minimal trackout. Permit is posted at entrance, perimeter silt fence in good condition.
|
Complaint Inspection | 4/24/2014 | 4/24/2014 | 4/24/2014 | P | CANC |
Andy J. Long
|
|
|
Data entry error. Please disregard.
|
General Inspection | 4/9/2014 | 4/9/2014 | 4/9/2014 | | PASS |
Andy J. Long
|
|
|
No significant trackout onto Ekhart. Grading and grubbing to the north of the wetland area has begun. No corrections at this time.
|
General Inspection | 3/25/2014 | 3/25/2014 | 3/25/2014 | | PASS |
Andy J. Long
|
|
|
The improved construction entrance has been effective in reducing trackout to Eckart. Some stockpiling/loading is in progress as well as some grubbing/grading in the NW corner of parcel. No corrections needed at this time.
Perimeter BMPs and stormwater facility protection is in good condition.
|
Tracking Control | 3/6/2014 | 3/6/2014 | 3/6/2014 | A | PASS |
Andy J. Long
|
|
|
Lucky Harris 13 has come back into compliance after the CN issued on 3/4.
Corrections made: 1. More rock of larger size added to construction entrance. 2. Wattles placed across Eckart to protect drainage ditch. 3. Road, gutters, and tops of curbs have been cleaned. 4. Site is on currently restricted during this week of precipitation.
The CN was removed today.
|
Tracking Control | 3/4/2014 | 3/4/2014 | 3/4/2014 | A | FAIL |
Andy J. Long
|
|
|
Correction notice posted:
1. Replenish construction entrance. Place geo-textile down to prevent mud from seeping up from pressure of dump trucks. 2. Install BMP on east side of Eckart to the south of the constrution entrance. Water and sediment flows to drainage ditch and river. 3. Continue daily sweeping as necessary.
Photos of violations have been taken. Written CN posted.
|
Tracking Control | 2/11/2014 | 2/11/2014 | 2/11/2014 | P | FAIL |
Andy J. Long
|
|
|
Excessive track out or spill of dirt/mud onto Eckhart. Will need extra sweeping/scraping at the end of the day. The construction entrance was enhanced but it still appears to be failing.
Issued verbal correction notice to RP. Second trackout warning/issue at site.
|
Tracking Control | 2/6/2014 | 2/6/2014 | 2/6/2014 | A | PASS |
Andy J. Long
|
|
|
Warner Construction improved their construction entrance as requested. It is now longer and has more rock. Trackout from previous week was swept up. No track out or other violations observed.
|
Random Inspection | 1/30/2014 | 1/30/2014 | 1/30/2014 | P | FAIL |
Andy J. Long
|
|
|
Significant track out on Ekhart road in both directions originating from the construction entrance. Sweeping will need to occur more frequently or a better construction entrance needs to be provided.
Verbal CN given to RP Chad Hamel. Left VM
|
Site Preparation | 1/16/2014 | 1/17/2014 | 1/17/2014 | P | PASS |
Andy J. Long
|
|
|
Chad Phone #: ###-####
Pre-con meeting with the following: ESC division and PW Grading Jason Taylor. 1. Warner Construction 2. Hunter Homes 3. Syman Company 4. TO Engineers 5. Strata Geotech
Discussed project and conditions of ESC permit and scope of work. Fill material initially to be trucked in from JUMP. All BMPs and construction entrance must be installed before shipments.
No disturbance of wetland area allowed, keep 50 foot buffer designated.
Inspection of silt fence BMPs and SWPPP binder found them satisfactory.
Project will begin over the next week and proceed in 100x100 ft phases.
Warner Construction stated a sweeper will be onsite to address trackout to Eckart.
Approved for construction.
|