General Inspection | 8/7/2020 | 8/10/2020 | 8/11/2020 | P | PASS |
Andy J. Long
|
|
|
Small landscaping crew active on upper area and entrance at Trent Point. Water line crew for separate project is also still active in the area.
Dry conditions, no trackout or discharges observed. New stormwater system is complete. Needs further inspection to assess revegetation status..
No correction requests at this time.
|
General Inspection | 7/31/2020 | 7/31/2020 | 8/7/2020 | | CANC |
Andy J. Long
|
|
|
|
General Inspection | 7/16/2020 | 7/16/2020 | 7/22/2020 | P | PART |
Michael Zawacki
|
|
|
Washout has been dumped at end of paving on asteroid. L2 doing some trench work on interstellar, looks like they are installing ads perf pipe. Vortex is paved going down hill, curb and sidewalk completed, crew on site cleaning sidewalk. Filter fabric removed from vortex pond, more riprap has been installed and flow areas reinforced with bigger rocks. No water on site. Message sent to RP about washout, only issue at site.
|
Conference | 7/9/2020 | 7/9/2020 | 7/9/2020 | P | DONE |
Andy J. Long
|
|
|
Update on project provided by RP Steve with CMG.
Vortex street is prepped for curb, gutters, and paving will start to begin. Concrete trucks will be directed to use the washout pan located in the upper section.
New and reconstructed ponds and stormwater features at Vortex and Ridigepoint to the site discharge point is now complete and has been hydroseeded. The plan is to install supplemental irrigation to keep grass growing through the hotter summer months.
The outlet pipe to the new reservoir will remian plugged until the sediment forebay, holding area, and surrounding slopes have properly revegetated.
No complaints or issues recently reported or observed. Dry weather conditions currently.
|
General Inspection | 6/30/2020 | 6/30/2020 | 6/30/2020 | P | FAIL |
Michael Zawacki
|
|
|
post rainfall inspection Trackout at vortex from sidewalk company. No water in vortex pond. Some water in reservoir, no dewatering. East pipe discharge 52.3 NTU. Flume NTU at JH yard 62 NTU. Pipe under Warm Springs 12.5 NTU Only issue at site is trackout, truck and trailer still at site.
|
General Inspection | 6/23/2020 | 6/23/2020 | 6/23/2020 | P | PASS |
Andy J. Long
|
|
|
Dewatering discharge turbidity sampling and site meeting to check differences in readings between City turbidimeters and site turbidimeters furnished by Syman Company.
Sampling results for 8:50- 9:25 AM:
Pen Can background: 3.75- 5.3 NTU dewatering water before discharge into canal: 319-361 NTU
Sample of visible plume of dewatering in discharge in Pen Canal 49.1-57.7* NTU.
* Syman test on same grab sample: 29.8 -30.5
Sampling results of dewatering system: -water detained in pond: 128- 138 NTU -water after passing through sediment bag and wattle: 85.1 - 92 - dewatering water entering unnamed stream at flume: 109
Additional sampling at 11:30 - 11:40 AM
- Pen Can background: 3.94 NTU - Dewatering water before discharge into canal: 129 NTU
Sample of visible plume of dewatering in discharge in Pen Canal 34.5 NTU .
The discharge at the recieving water at 11:40 AM was in compliance, increasing turbidity of water in Pen Canal by approximately 31 NTU.
Conclusion: Dewatering is being treated but then picks up turbidity between the discharge at the site and the discharge into the receiving water, Pen Canal. Mud and eroded sediment from the site and other source is being flushed by the dewatering water. The visible plume when compared to background is in compliance.
Dewatering should be completed by tomorrow if not today. Once pond is dewatered site will continue with stabilization and revegetation of the remaiing disturbed areas. Syman is taking sample visble plume grab sample that all four meters (Boise (2), ACHD (1), Syman (1)) tested. If taken within 48 hours and successfully kept below high temperature, the result could be meaningful in determining why Hach turbidimeters used by City and ACHD get different (higher NTU) readings than the Lamotte meter used by Syman.
|
General Inspection | 6/22/2020 | 6/22/2020 | 6/22/2020 | A | PASS |
Andy J. Long
|
|
|
Dewatering in progress. Pumping from plugged resevoir holding captured stormwater from last weeks rain events.
Conducted turbidity sampling at the discharge point of the unamed stream from the Mesa into Penitentiary Canal at Warm Springs Road:
Background water upstream in Pen Canal of discharge point at Warm Springs Road: 3.91 NTU @ 12:26 PM
Water in unnamed stream prior to discharge to Pen canal: 152 NTU @ 12:28 PM
Water downstream in Pen Canal after discharge: 47.6 NTU @ 12:38 PM (this is still in compliance being less than 50 NTU increase of background water)
Other measurements:
Water flowing from Pen Canal into culvert to ACHD pont 9.83 NTU
Water joining stream after passing through dewatering bag, passing through vegetation and controls installed was 104 NTU @ 12:51 PM
Water in site stormwater holding pond 171 NTU @ 1:03 PM Water below dewatering bag 100 NTU @ 12:58 PM Double check of water in bottom of stream prior to discharge to Pen Canal: 149 NTU @ 13:28 PM
The dewatering water is actually getting dirtier (more turbid) as it travels down stream picking up residual mud from previous runoff events and perhaps due to the steepness of this section of stream.
This inspection is a PASS because the background and downstream turbidity at the discharge point is less than 50 NTU and the dewatering water is clear to the naked eye where it is joining the unnamed stream and the system is effectively reducing the turbidity of the water from the holding pond, allowing for the discharge to continue.
Follow up inspection scheduled tomorrow with ACHD and Syman to conduct turbidity testing with different meters to compare results.
|
General Inspection | 6/19/2020 | 6/19/2020 | 6/19/2020 | P | PEND |
Andy J. Long
|
|
|
check on dewatering
Pump turned off. Site is going to allow for more settling and pump on Monday. Request to check turbidity of detention pond surface, and then turbidity of dewatering discharge to the flume/stream that carries water offisite towards Boise River.
Follow up Monday
|
General Inspection | 6/18/2020 | 6/18/2020 | 6/18/2020 | P | FAIL |
Michael Zawacki
|
|
|
Follow up on dewatering set up and turbidity Turbidity reading. East pipe on dam 73.8 NTU Creek at start of flume 73.8 NTU Creek at exit pipe at JH parking area. 180 NTU. Dewatering water above flume 187 NTU Dewatering water below bag 248 NTU.
While on site I adjusted the hose by placing it further into the bag. The water than flowed through more of bag. After about 10 minutes NTUs out of bag dropped to 231. Water exeting site is still to high from background, results in failure and illicit discharge.
|
General Inspection | 6/18/2020 | 6/18/2020 | 6/18/2020 | P | PEND |
Andy J. Long
|
|
|
Wednesday 6/17 5 PM follow up inpsection on dewatering system.
Dewatering pump was turned off at time of inspection. Additional velocity and filtering controls were install downslope of the dewatering bag and the water in the pond will be allowed to settle overnight. Notified RP they are approved to resume dewatering but that the water cannot increase turbidity by over 50+ NTU as it was on Tuesday and Wednesday AM
Turbidity measurements:
- 4:48 PM site discharge pipe 95.1 NTU - 4:47 PM downstream from site discharge and rip rap: 91.1 NTU - 4:35 PM bottom of hill @ Warm Springs Road before discharge into slough 52.4 NTU
Will collect samples of dewatering 6/18
|
General Inspection | 6/17/2020 | 6/17/2020 | 6/17/2020 | P | FAIL |
Michael Zawacki
|
|
|
Did turbidity sample on site. Meter is calibrated, certified by manufacture, and less than 30 days old. Trent Point Inlet :146 NTU Vortex inlet : 51.4 NTU Vortex Pond Surface: 67.5 NTU Vortex Pond Outlet: 104 NTU Dame Face East Pipe:95.9 NTU Dam Face West Pipe: 82.7 NTU Creek Below Dam: 134 NTU Flow Under Dewatering Bag from Reservoir Dewatering: 489 NTU Flume where dewatering water joins creek: 262 NTU Site is out of compliance. Water turbidity was 146 NTU in, 262 NTU out. Increase of 116 NTU.
|
General Inspection | 6/17/2020 | 6/17/2020 | 6/17/2020 | P | PEND |
Andy J. Long
|
|
|
Tuesday 6/16 3 PM
check on dewatering setup and take turbidity samples
Turbidity samples: - Ridgepoint/Vortex pond inlet pipe (upstream background) : 29.6 NTU - Ridgepoint/Vortex pond water at outlet end (not manhole) : 67.6 NTU - End of site discharge outfall in pipe : 92.1 NTU (+ 62 NTU over background) - Downstream from riprap: 95.5 NTU - In stream after water from dewatering joins flow: 330 NTU (300 NTU over backgroud) - At stream at outfall to slough @ Warm Springs Road 271 NTU
Observations: - dewatering pontoon installed and pump running. Energy dissipation on geotextile and wattle installed properly as requested. Water has not settled enough in pond and flows down hill too fast for vegetation to filter - dam face is continuing to rill. Too wet for maintenance at this time, site has plan to fix when possible. Dewatering hose leaks have started a new rill in between a section of wattle, muddy water enterining riprap at outfall.
Corrective actions: - make changes to dewatering system to get water within less than 50 NTU of background (site has turned off pump after being notified of discharge turbidity and is working on plan, follow up scheduled) - need to address erosion on dam face and sediment running off dam into riprap and beyond
Discharge is not in compliance.
Site is in process of corrective actions. It has been raining everyday and site conditions are preventing maintenance.
|
General Inspection | 6/15/2020 | 6/15/2020 | 6/17/2020 | P | PASS |
Andy J. Long
|
|
|
post rainfall inspection
Monday 6/15 turbidity testing:
- background into vortex/Ridgepoint pond: 49.8 NTU - Vortex/Ridgepoint pond outfall manhole: 81.5 NTU - Site stormwater outfall to stream: 78.8 NTU - Downstream below riprap: 71.6 NTU. The discharge at time of inspection was with water qualtiy limit and in compliance.
Observations:
- the corrective action taken by site to clean out all manholes and stormwater bypass system seems to have eliminated the issue of water entering the pipe from the pond and then stirring up deposited mud/sediment in each manhole junction.
- no significant issues observed in upper section of subdivision. Good vegetation, streets paved, silt fence and vegetated buffer perimeter - stormwater running down Ridgepoint into the pond comes at too great of velocity and volume for the existing riprap spillway in front on the storm drain drop inlets. Erosion occurs on the spillway into the pond - rilling has started to occur on the dam face and wattle maintenance is needed. No sign of any of the recent seeding application growing. Lots of dirt and mud has been deposited into the center rip rap. No sediment control at bottom end of dam above outfalls. - Syman onsite for turbiditiy testing and results put in SWPPP - dewatering out of plugged resevoir into upland vegetation has been approved. Request to place pump hose on pontoon to get top of water column, putting energy dissipation at hose outlet and direct water down existing draw. Did not request to attach silt bag at end of hose in worry of plugging and malfunction.
Correction request: - schedule wattle mainteance and installation on dam. Apply temporary tacifier or re-seed with mulch.
|
General Inspection | 6/9/2020 | 6/9/2020 | 6/9/2020 | A | PEND |
Andy J. Long
|
|
|
Follow up turbidity testing conducted to determine source of increase in turbidity between Ridgepoint Pond through bypass pipe system to the site outfall.
Testing conducted with brand new Hach 2100Q turbidimeter, full calibration completed 6/8 as well as the older Hach 2100Q used for previous turbidity measurements
Results: background inflow to Ridgepoint Pond - no flow at time of inspection (dry conditions, no discharges from water line project)
Ridgepoint pond surface water near outlet: new meter 20.7 NTU; old meter 22.2 NTU
Ridgepoint pond outlet manhole before entering bypass pipe: new meter 57.5, old meter 59.5
Bypass water sample dropping into manhole that has 12" connection from lower pond and the 12" outfall pipe: new meter 50.3 , old meter 57.6. * no significant change from pond outlet manhole.
Water in detention dam with capped outflow pipe: new meter 383 NTU, old meter 427 NTU
Outfall in pipe : new meter 176 NTU, old meter 198 NTU
Conclusion:
bypass water from Ridgepoint Pond is getting additional flows either from muddy groundwater interflow/inflow in manhole, or the detention pond cap is allow some of the high turbidity water to flow out and join the bypass water. At the final manhole water increased turbidity from 50.3 NTU to 176 NTU. With no official background water flowing into site to compare to, this is still a visibly turbid discharge offsite. Roadway stormwater runoff in this area (when not polluted by another construciton site) has been previously tested to be between 20-50 NTU
Notified site stormwater of finding.
Correction requests: - fix issue with manhole or detention pond cap - install sediment control wattle at the perimeter edge of the dirt slopes just above the outfall pipes and outfall rip rap and spread some mulch or seed to stabilize the currently bare ground.
|
General Inspection | 6/8/2020 | 6/8/2020 | 6/9/2020 | P | PEND |
Andy J. Long
|
|
|
Post rainfall turbidity testing conducted with site RP Steve and Syman Company
Prior to these samples, testing with Syman company found a descrepency between the two meters. See turbidity log in SWPPP for syman readings
3 point calibration on meter prior @ 12:05 20 NTU standard : 20.2 on meter 100 NTU standard: 95 on meter 800 NTU standard: 786 on meter
Water coming into Ridgepoint Pond from stormwater inlet pipe @12:09: 633 NTU* dirty from water line project uphill. Very low flow, from dewatering/water line break
Pond water near the Ridgepoint Pond outlet pipe 31.7 NTU
Water coming out of site final outfall before entering rip rap section & stream: 161 NTU (472 NTU less than dirty background water from Granite/Suez project; 129 NTU more than Ridgpoint pond surface water at outlet)
Downstream from site outfal rip rap 146 NTU
Ridgepoint pond water quality has been negatively effected by runoff from the Granite/Suez site. ACHD notified, should be responsible for cleaning out storm drains and replacing the geotextile, flushing the riprap.
However water for the Ridgepoint pond outlet does get dirtier by the time it discharges at the site outfall potentially due to water mixing in dirty sumps in manholes and/or a leakage of the plugged resevoir joining the bypass water flow.
Investigation in progress
|
General Inspection | 6/8/2020 | 6/8/2020 | 6/8/2020 | P | FAIL |
Andy J. Long
|
|
|
Post rainfail turbidity inspection conducted 4-5 PM Sunday June 7 after significant rain event
Water coming into Ridgepoint Pond from stormwater inlet pipe: 45.5 NTU
Water near the Ridgepoint Pond outlet pipe 42 NTU
Water coming out of site final outfall before entering rip rap section & stream: 218 NTU (increase 175 NTU over background water)
10 meters Downstream from site outfall rip rap: 215 NTU
Additional measurements taken offsite:
Downstream from site in creek @ Starview curve 190 NTU
ACHD stormater channel by East Parkcenter Bridge 25.4 NTU
Outlet into Walling Creek/Boise River side channel 16.8 NTU
Boise River tested upstream @ Barber Park 2.4 NTU
Inspection was turbidity testing only, post rainfall site inspection is in progress.
|
General Inspection | 5/28/2020 | 5/28/2020 | 5/28/2020 | P | PASS |
Michael Zawacki
|
|
|
Paving crew on upper section. Water truck is spraying road bed. Crew working on sewer line coming down vortex. Vortex pond is empty, newly installed geotextile already covered in dirt from utility work runoff coming from different project. Bare areas above pond and by inlet have been hydroseeded. Crew working on grade below vortex heading to reservoir pond. Pond is now split into two bays. Backside of dam has been hydroseeded. Very small amount of water coming out pipe and running down creek, is not turbid. No dust but will need to be monitored and watered if needed.
|
General Inspection | 5/21/2020 | 5/21/2020 | 5/22/2020 | P | PEND |
Andy J. Long
|
|
|
Turbidity sample taken @ 4:30 PM Friday 5/22 downstream from rip rap at the outfall 83.3 NTU. Water is almost drained out of the pond. Water is visibly clear coming out of the pipe.
Sample at Warm Springs Road @ 4:40 was 10.5 NTU.
No activity at site. Loose dirt on Ridgepoint by pond needs to be cleaned up. No water coming into pond to test background turbidity.
|
General Inspection | 5/19/2020 | 5/19/2020 | 5/21/2020 | P | CANC |
Andy J. Long
|
|
|
|
General Inspection | 5/20/2020 | 5/20/2020 | 5/21/2020 | P | FAIL |
Andy J. Long
|
|
|
Rainfall event inspection 12 - 3 PM continued from AM inspection. Raining most of the day with runoff continuing to flow onsite and on surrounding streets - inspected upper area, no berm blowouts or perimeter breaches observed - Source of muddy runoff the road mix prepped for paving and that the storm drain pipe down Vortex is not complete. - Sand bags installed to minimize muddy water leaving at Trent Point have reduced flow offsite. - Syman onsite inspecting and taking turbidity samples which are entered in SWPPP
Turbidity testing @ 1:30 PM
Background stormwater turbidity going into pond: - inlet pipe to pond 206 NTU - gutter at Ridgepoint and Stone Ridge 102 NTU
Outfall and stream at bottom of site: - In pipe from pond 157 NTU - in pipe from lower Mesa streets 29 NTU .... turbidity and flow suddenly increased during testing. Rip-rap splashing water onto the unstabilized dirt around outlet pipes and eroding soil. Sample at bottom of rip rap 552 NTU
Discovered source of surge of muddy water was the ball valve in outlet pipe from detention dam failed. Muddy water that had been detained onsite discharged. RP Steve and L2 crew were able to cap the outlet pipe in the pond to stop discharge. Pond was uncapped for approx. 2 hours
Turbidity samples at bottom of hill on channels leading towards river: 2:25 PM ACHD stormwater channel 87.4 NTU 2:30 PM outfall to wetland river channel 74.3 NTU 2:35 PM in stream just above Warm Springs Road 796 NTU
Correction requests: - park asphalt mixer within site, not on street entrance. Water pooling in asphalt bin and leaking out, slight sheen observed - clean up spill/sheen near asphalt machine (could be from Suez/Granite job as well) - inspect site tomorrow for issues and turbidity testing - need to stabilze/cover the dam face within 10 ft radius around the two outfall pipes to prevent splash back from rip rap and erosion in this area - clean up any loose dirt on Ridgepoint around storm drain to pond - file corrective action report in SWPPP - once stream no longer has flow, need to inspect and clean up mud accumulations
|
General Inspection | 5/20/2020 | 5/20/2020 | 5/20/2020 | A | FAIL |
Andy J. Long
|
|
|
Rainfall inspection. 9:45 AM- 12 PM. Approximately 0.6-1.0" rain received on site within previous 24 hours. Muddy stormwater discharging at bottom of site
turbidity sampling @ 10 - 10:30 AM
Background stormwater turbidity going into pond: - inlet pipe to pond 199 NTU - gutter at Ridgepoint and Stone Ridge 102 NTU
Outfall and stream at bottom of site: - In pipe from pond 661 NTU - downstream 30 ft from end of riprap 642 NTU - downstream before culvert to flume 696 NTU
* increase in turbidity attributed to mud and dirty stormwater already in pond due to issues on the separate water pipe replacement project runoff (permitted through ACHD)
Observed muddy runoff leaving main site entrance at Trent Point which does contribute to the runoff that flows into the Ridgepoint/Vortex pond (tested @ 646 NTU in gutter)
Significant flow of muddy water from the upper section of site flowing down the uncompleted Vortex Road and is being retained onsite in the resevoir/pond to prevent discharge of this muddy water offsite without settling/treatment. Pond appeared to be holding water and filling during the AM inspection.
Correction requests: Prevent dirty water from running offsite at Trent Point entrance. Install sand bags and gravel bags to prevent water from running offsite and down gutter at and instead into the new DIs that keep water onsite. (task completed during inspection) - more correction requests pending post rainfall. Still raining.
Reviewed SWPPP:
- Revisions made to SWPPP satisfy Boise ESC correction requests related to SWPPP. - turbidity log is being kept in appendix L. Turbidity testing must occur during all rainfall event inspection.
Note: Inquiry on official WOTUS status of receiving surface water at bottom of site sent to IDEQ and EPA on Monday 5/18, waiting for response.
|
General Inspection | 5/14/2020 | 5/14/2020 | 5/14/2020 | P | FAIL |
Andy J. Long
|
|
|
SWPPP corrections not complete as requested. No request for extension or communication from SWPPP plan designer.
No updates found in onsite SWPPP or in the online link to the project folder.
Correction requests for SWPPP already issued 5/7:
- Update the 1-mile radius receiving waters map, does not show the correct flow route of water from the site - Update/revise the incorrect information regarding buffer exceptions on page 16 - Update ESC site map showing all current BMPs, areas where stabilization is not yet implemented, and turbidity monitoring locations - Have all corrective action reports in onsite SWPPP (or send links) - Have updated turbidity measurement log in appendix L of SWPPP showing past data and a log table to record new data - Follow notification requirements per the CGP permit information on discharges exceeding WQS to Water of the US. List requirements in SWPPP on turbidity log paperwork.
syman SWPPP link:
https://drive.google.com/drive/folders/1Wpdx4GULVj0t4ykgXzPg19WHWuvuhg3w
|
General Inspection | 5/6/2020 | 5/11/2020 | 5/14/2020 | A | PASS |
Andy J. Long
|
|
|
Post rain event turbidity testing
Background water samples flowing into pond - from pipe flowing into pond 488 NTU - water coming out of pipe from new DIs on Ridgepoint 997 NTU - water in gutter upstream at Coloma & Stone Point 960 NTU
Discharge samples - Ridgepoint pond outlet pipe 127 NTU - Outlet pipe for water from existing subdivsion draining from lower Ridgpoint 52.7 NTU - downstream from rip rap outlet controls 174 NTU - water in flume 177 NTU
Source of turbidity in the background sample is road work from Granite Excavation for Suez pipe replacement. Not related to this project. Has ACHD and CGP SWPPP coverage, no City ESC permit due to being ROW. Notified RP Rhett with Granite and ACHD inspector. Issued verbal corrections to provide sediment controls and cover for stockpiles and to clean out all downstream sediment controls. Have sweeper unit onsite. Keep loose dirt out of gutters, sidewalks, and road.
It appears that the stormwater system and changes is reducing turbidity of the water. Took sample at bottom of hill by Warm Springs Road in Mesa UIS @ 10:30 AM after the rain stopped and turbidity was 12.5 NTU. No plume observed in Walling Creek.
|
Conference | 5/7/2020 | 5/7/2020 | 5/7/2020 | P | DONE |
Andy J. Long
|
|
|
Correction requests for updatig ESCP/SWPPP sent to site stormwater team via email.
Corrections need to be submitted by 5/14/2020: - Update the 1-mile radius receiving waters map, does not show the correct flow route of water from the site - Update/revise the incorrect information regarding buffer exceptions on page 16 - Update ESC site map showing all current BMPs, areas where stabilization is not yet implemented, and turbidity monitoring locations - Have all corrective action reports in onsite SWPPP (or send links) - Have updated turbidity measurement log in appendix L of SWPPP showing past data and a log table to record new data - Follow notification requirements per the CGP permit information on discharges exceeding WQS to Water of the US. List requirements in SWPPP on turbidity log paperwork.
|
General Inspection | 5/4/2020 | 5/4/2020 | 5/6/2020 | P | CANC |
Andy J. Long
|
|
|
|
General Inspection | 5/4/2020 | 5/4/2020 | 5/4/2020 | P | PASS |
Michael Zawacki
|
|
|
Follow up to check progress after Friday meeting. New riprap lined channel to vortex pond from street. Syman has installed new wattle perimeter along pond perimeter. Crew is now removing old dirty geotextile and will replace it. Riprap installed on outlets below dam. Crew working on dam, looks like they are starting emergency spillway. Crew is removing old plastic diversion pipe, unable to verify but looks like new drainage is connected. Crew also inspecting new pipe.
|
General Inspection | 4/30/2020 | 5/1/2020 | 5/1/2020 | P | PEND |
Andy J. Long
|
|
|
Onsite meeting at 9:30 AM to discuss corrective actions after discharge of muddy stormwater due to signifcant rainfall and BMP failures ( inadequate outlet protection on new stormwater system features at Vortex/Ridgepoint pond and outfall at bottom of site, plugged/misconnected stormwater bypass pipe)
Corrective active plan: - all work Friday and Saturday is focused on repair and preparing system to be properly operational - repair/complete the new stormwater discharge pipe into pond so no erosion occurs when flowing into pond - build lined & rip rapped spillway upstream from new DIs on Ridgpoint to prevent overflow from gutter over disturbed ground to pond
- add additonal lining to hold down sediment and perimter sediment controls around the Ridgepoint/Vortex pond to ensure no flows from disturbed areas around pond so all water going in is treated by a sediment control
- Plug outlet pipe from the pond ASAP to create a no discharge situation till system can be properly completed; will be plugged until system completion (monday-tuesday 5/4-5/5). Will need to be onsite if rain storm occurs (none currently forecasted) to make sure pond does not overflow - repair broken manholes and make connections per plan. Verify correct connection once complete - Install outlet protection (energy dissipators, scour prevention, rip rap, flow spreader etc) at bottom of site - clean out any accumulated mud in the stormwater drainage system and below the site discharge. Remove mud on cement flume passing by JH storage lot - take turbidity measurements and plan for turbidity testing of stormwater discharges after all 0.25 rain events until further notice. keep log in SWPPP - complete corrective action report for SWPPP, share link to Syman website for the site's SWPPP with Boise ESC Inspectors for review
Follow up scheduled for Monday 5/4
Turbidity testing conducted: - 9:10 ACHD stormwater basin at bottom of Starcrest prior to discharge to Boise River tributaries 44.7 NTU - 9:15 Boise River tributary channel approx 1/3 mile downstream 37.2 NTU - 9:40 Water pooled in Vortex/Ridgepoint pond 647 NTU - 10:00 Bypass outlet pipe 968 - 10:05 down stream from outlet pipe in creek before flow into culver to flume 793 NTU - note: estimate Boise River is no more than 5 NTU. This is an exceedence of water quality limits
Note: upper subdivsion is in compliance. No trackout, consturction entrance installed, concrete washout pan, bermed lotsf for stormwater control, revegetation looks really good
follow up scheduled for Monday
|
General Inspection | 4/30/2020 | 4/30/2020 | 4/30/2020 | P | FAIL |
Andy J. Long
|
|
|
post rain inspection
Thunderstorm conditions with > 0.3" in one hour passed over site.
No hillside or slope erosion within site. Water from new subdivsion areas is contained on site by grading/channeling on Vortex to the detention ponds behind dam (no outlet).
Stormwater from existing roads and stormwater system is flowing into the pond at Ridgepoint and Vortex which has been under re-construction and expansion. Stormwater is picking up turbidity in this pond since it is not yet complete and previous attempts to line the bottom of the pond to keep accumulated sediment down have not worked.
Outlet pipe from pond is supposed to be connect only to the bypass pipe, instead water is surfacing out of manhole , flowing over disturbed area into the old section of creek and into the new stormwater pipe which does not have the proper outlet protection and additional erosion is occuring at the outlet. Bypass pipe must not be connected correctly or is plugged, only small amount of the water is going through the bypass.
Correction requests:
- connect pipes to new stormwater system so water leaving the pond does not go to surface - install outlet protection (rip rap, lining) to prevent erosion at the discharge point of all pipe outlets at bottom of site. - work on way to prevent stormwater from existing system from getting dirty in the unfinished pond - write corrective action report for SWPPP - have turbidimeter onsite until completion to take readings of every discharge
Discharge was muddy at bottom of site. Muddy water was observed flowing into Walling Creek which is connected to the Boise River. - Consider increasing retention time in Ridgepoint/Vortex pond of having a valve to stop flows once rain has stopped to let water settle/pump out down to resevoir.
Investigation, corrective actiions, and enforcement is pending.
RP was onsite working to make corrections and order labor and supplies for tommorrow.
Follow up scheduled.
|
General Inspection | 4/23/2020 | 4/23/2020 | 4/23/2020 | P | FAIL |
Michael Zawacki
|
|
|
Curbing and sidewalks done on first phase of upper section, road bed installed and not paved. Grass is growing very well. Ridgepoint is closed, crew on site. Met with Mark, Dave, and Steve on site. Part of bypass pipe may be blocked or broken. Water is coming out of sewer top, running into creek, and into new line being installed. Water is ending up behind dam instead of around it. L2 is doing minimal work today since it is to wet. They want to have sewer connection done within 7 days. Took turbidity readings: Pond on Vortex 308 NTU Bypass below dam 481 NTU Creek outflow at bottom of site: 373 NTU. Creek between overflow and dam, all stays on site :658 NTU Everyone was notified of issue, working on solutions.
|
General Inspection | 4/20/2020 | 4/20/2020 | 4/20/2020 | P | PART |
Andy J. Long
|
|
|
check for any dust issues
Report of no water trucks onsite.
Two water trucks parked on site (one for L2, one for Central Paving), some areas of dust generation. No consistent plumes or wind blown dust.
Request to have water trucks cycle over haul roads and dust areas at least once every 1-1.5 hours.
|
General Inspection | 4/15/2020 | 4/15/2020 | 4/15/2020 | | PASS |
Andy J. Long
|
|
|
No trackout or discharges from subidvsion. No water or runoff leaving site or in creek.
WIP on Ridgepoint to install new storm drains and sewer connection for Vortex.
Correction request to fix silt fence section above the BH #6 pond and below the trent point entrance.
|
General Inspection | 3/30/2020 | 3/31/2020 | 4/1/2020 | P | PASS |
Michael Zawacki
|
|
|
No wate rin vortex pond or above dam. L2 is on site at bottom of road working on sewer. Few trenched dug, extra boxes and chips on site. Gras is starting to grow on hillsides. Concrete crew on top installing sidewalks and curbing. Sidewalks LLC is contractor, Knife River is bringing mud. Did not see any concrete washout or dumped washout at site. No ESC issues
|
Complaint Inspection | 3/23/2020 | 3/23/2020 | 3/23/2020 | P | PASS |
Michael Zawacki
|
|
|
Plastic sheeting was pulled up from wind. Area affected was inside reservoir area behind dam, lining on road was all in place. I pulled the liner back up and weighed down the seam with rocks, rolled boulder on lower section of plastic to keep the wind from blowing it off. There was never a risk of discharge.
|
General Inspection | 3/16/2020 | 3/16/2020 | 3/16/2020 | P | PASS |
Michael Zawacki
|
|
|
No tracking, no failures, equipment all staged by trent point entrance. Vortex pond 67.1 NTU Outlet below dam 102 NTU Creek at end of project 94.5 NTU Could not find where water was picking turbidity on site.
|
General Inspection | 3/12/2020 | 3/12/2020 | 3/12/2020 | P | PASS |
Michael Zawacki
|
|
|
No water in vortex pond or above dam. Info board on street saying it will be closed for work 3/16-3/20. New construction entrance at top. Road bed and sidewalks being prepped, looks like they are getting ready for curb sidealk and paving.
|
General Inspection | 3/3/2020 | 3/3/2020 | 3/3/2020 | P | PASS |
Andy J. Long
|
|
|
Minor activity prepping sidwalk and gutter areas on upper section.
NO trackout or discharges from site. Dry conditions.
Corrections needed:
- repair/reinstall silt fence below main entrance & above phase 6 pond - pick up loose trash at the discharge point. Stuck in bushes - remove dewatering bag
|
General Inspection | 2/18/2020 | 2/18/2020 | 2/18/2020 | P | PASS |
Michael Zawacki
|
|
|
post rainfall inspection Turbidity monitor calibrated before inspection. Vortex ponbd 50.7 NTU Pool behind dam 72.9 NTU Outlet below tree 70.5 NTU Creek before leaving site 74.1 NTU. Boise River at Barber Park is 1.85ntu.
No dewatering, no pump on site. New check dams installed coming down road at 25' spacing. Bottom of hill is all gravel, road from vortex pond to dam has been lined in poly. No backup on road, no left behind sediment. No new rilling or failures noticed.
|
General Inspection | 2/14/2020 | 2/14/2020 | 2/14/2020 | P | PASS |
Andy J. Long
|
|
|
Additional BMPs added to site in response to preveious rain events and to prepare for forecasted rain and snow.
Added rock check berms/dams to Vortex and graded out the rills. Installed sheeting from Ridge Point pond down to the detention pond to prevent erosion and reduce turbidity of the water in the detention pond. Construciton entrance on Ridge Point has been improved.
No dewatering or pumping occuring. Water coming out the bypass discharge pipe is clear. No trackout or discharges, no crews onsite at time of inspection.
If dewatering is needed, will need to relocate the dewatering bag. There is some erosion occuring on some steeper sections of the slope where the water flowed over. Corrections needed:
Need to repair silt fence above the phase 6 stormwater pond, clean up trash and wrappings in the bushes at the bottom of the site.
|
General Inspection | 2/7/2020 | 2/10/2020 | 2/11/2020 | P | PASS |
Michael Zawacki
|
|
|
No activity at site, not currently dewatering. Starting to see flow lines under dewatering bag, continued dewatering may start to cause rilling on hill. Messured turbity: Vortex Pond 71.2 ntu Ponding behind dam 75 ntu Outlet pipe below tree 39.4 ntu Creek befor leaving site 34.3 ntu No water coming out of first pipe directly below dam
|
General Inspection | 2/7/2020 | 2/7/2020 | 2/7/2020 | P | PEND |
Andy J. Long
|
|
|
Friday morning 1###-####
Follow up inspection and turbidity testing
Minimal overnight rain, Pond water was murky and did not appear to have settled much. Runoff no longer flowing. Pump was not running. RP Steve on duty.
Turbidity testing: - bypass pipe dicharge to drainage 149 NTU (not in compliance, down from 260 NTU sampled Thursday) - storm drain outlet pipe from existing subdivsion from Ridgepoint 70 NTU - Approximately 75 yards down stream in drainage: 134 NTU - Ridge Point pond water 156 NTU - pond inlet water 50 NTU - curb water draining into pond 54 NTU - BH # 6 stormwater pond outflow 49 NTU
Correction requests:
- continue to pump down turbid water out of stormwater pond down to reservoir to reduce amount of water able to flow offsite through bypass pipe - clean gutter along Ridge Point and the storm drain on Stone Ridge that drops into pond - install sediment controls at construction entrance on Trent Point - fix silt fence sections that have come untrenched above the BH # 6 stormwater pond - rebuild berms or install silt fence perimeters around the 2 lowest lots at top Vortex intersection - repair Vortex check dams and/or provide road mix base
Did not observe any significant slope erosion or issue within the subdivision. Silt fence permeter and vegetative buffer are effective. Possible that the slow settling turbidity in the pond could be from the crushed rocks used to line the pond or mix of deicing agent placed on roadways.
Follow up scheduled for Monday 2/10
Note: incident reported 1/28 was caused by setting a dewatering hose out without energy dissipation. Disturbed bank has been covered and will be repaired later. Dewatering hose attached to a sediment bag and placed uphill on the grass.
|
General Inspection | 2/7/2020 | 2/7/2020 | 2/7/2020 | P | FAIL |
Andy J. Long
|
|
|
Follow up inpsection from 4-5 PM to conduct turbidity testing.
The flow of muddy water into pond had been stopped by earthwork and redirected to flow downhill to the no-outlet reservoir for settling - less than 1/4 full. Pump was running to suck water out of Ridge Point Pond down into the reservoir.
Turbidity testing results:
Ridge Point pond inlet (culvert outlet at uphill end of pond) is street runoff and from BH#6 stormwater pond : 52 NTU
Stormwater bypass outlet pipe of Ridge Point pond water: 260 NTU (not in compliance)
Bottom of drainage @ Warm Springs before entering stormwater channel/pond : 208 NTU
No plume observed at outlet @ Walling Creek
|
General Inspection | 2/6/2020 | 2/6/2020 | 2/7/2020 | P | FAIL |
Andy J. Long
|
|
|
Inspection conducted between 11:15-12:15 on Thursday 2-6
- muddy runoff flowing down Vortex overwhelmed checkdams and berms placed in roadway and at bottom hill. Muddy runoff was flowing into the pond at Ridge Point & future lower subdivision entrance. This pond also receives runoff from the surrounding streets and the Boulder Heights phase #6 stormwater pond at the upper end Stone Point - Observed turbid discharge at the bottom of site at the temporary bypass outlet into creek that flows to stormwater ponds/basins and then Walling Creek to the Boise River. Stomwater channel at bottom of hill was muddy. No plume to Walling Creek observed - Notified RP Steve to meet onsite. Made corrective action plan to block runoff from Vortex from flowing into the pond and instead to the subdivision reservoir that does not have an outlet. Also to dewater dirty water in pond by pumping to reservoir to settle and avoid further discharge of this water in the the pond.
|
Complaint Inspection | 1/28/2020 | 1/28/2020 | 1/28/2020 | P | DONE |
Michael Zawacki
|
|
|
Looks like dewatering is causing seepage and landslide below. Took pictures wil share with hillside engineer.
|
General Inspection | 1/27/2020 | 1/27/2020 | 1/28/2020 | P | CANC |
Michael Zawacki
|
|
|
|
General Inspection | 1/23/2020 | 1/23/2020 | 1/23/2020 | P | PEND |
Andy J. Long
|
|
|
Construction activity is on winter hold till April. Full walk through to be conducted, but no muddy runoff observe and BMPs are installed.
Correction needed: - update contact info on inspection reports - reinstall barricade. Appears there is more joyriding occuring and trackout from that.
Walk through next week.
|
General Inspection | 1/9/2020 | 1/9/2020 | 1/9/2020 | P | PASS |
Michael Zawacki
|
|
|
No new activity on lower section. Meltwater is flowing to pond with no issues, no water behind dam, no rills or issues. No issues on upper section.
|
General Inspection | 12/19/2019 | 12/19/2019 | 12/19/2019 | P | PASS |
Andy J. Long
|
|
|
No significant trackout on Trent Point entrace. Permit information and SWPPP is onsite.. Stormwater discharge from site at end of pipe is clear. Limited areas of rill/gully erosion will need to be repaired. New berms and silt fence (around Ridgepoint pond) have been installed to control the flow/direction of runoff.
Corrections needed: - update contact info for site contact in inspection forms; RP is not Eric Allen - last inspection report entered was 11/19. Need to provide recent inspections and rainfall event inspection - Need to pick up loose trash from insulated blankets/tarps around the lower dam area - There is area of silt fence below the Vortex junction that needs trenching and the tracking upslope from this spot is parallet to the downhill direction.
RP Steve notified of corrections. Will follow up on next inspection
|
General Inspection | 12/13/2019 | 12/13/2019 | 12/13/2019 | P | PASS |
Michael Zawacki
|
|
|
No activity at site. Lower pond has water, berm built at bottom of road to redirect flow into pond. Area is to muddy to walk.
|
General Inspection | 12/12/2019 | 12/12/2019 | 12/13/2019 | P | PART |
Andy J. Long
|
|
|
post rainfall inspection inspection 12 PM on 12/12
- Very muddy conditions on site, soil is saturated. Upper lots with terraces & berms held water. - no signs of new erosion or breaks in the tacifier crust on slopes that have been applied. - existing pond at Ridgepoint held water well, silt fence and rock bags have been lined along the gutter to prevent water cutting over disturbed area. - pond is holding water for sedimentation and slowly draining water. - water discharging at the final discharge point from the subdivsion was clear.
Corrections needed: - maintenance and additional rock needed at both construction entrances - need to post more no trespassing signs or block entrance when site is inactive, there have been some 4wd joyriders driving around the site and causing damage and trackout.
Notified RP Steve who had also done a post rainfall inspection.
|
General Inspection | 11/27/2019 | 11/29/2019 | 12/3/2019 | P | PASS |
Michael Zawacki
|
|
|
Rocks armor added to pond, wattle protecting transition from rock to dirt. No work on lower section, attempted to walk but to muddy. Some dirt being hauled into upper area for use on ponds, no earthwork being done. Roads have been lined with pit run, sweeper is working on roads at time of inspection.
|
General Inspection | 11/22/2019 | 11/22/2019 | 11/22/2019 | P | PASS |
Michael Zawacki
|
|
|
WIP on retention. Walked site to check for dust, runoff, or trackout. No issues, water truck on site, dump trucks using internal road to haul fill from top.
|
General Inspection | 11/13/2019 | 11/13/2019 | 11/13/2019 | P | PASS |
Michael Zawacki
|
|
|
Work has begun on pipe from upper pond. ACHD has approved new work and retention will soon be built.
|
Complaint Inspection | 11/8/2019 | 11/8/2019 | 11/8/2019 | P | PASS |
Andy J. Long
|
|
|
Dust complaint received
.
Some dust observed in areas of equipment activity. Road grader is grading road base.. No plumes leaving site.
There was no dust truck in operation during the inspection from 2:45-3:45.
Stormwater controls are in place.
Work to begin on the lower stormwater ponds on Monday.
|
General Inspection | 10/23/2019 | 10/31/2019 | 10/30/2019 | P | PASS |
Michael Zawacki
|
|
|
Did site walk through. Upper channel has been lined with boulders, finishing by putting some large rock checks in. Area on hill has been tracked, scheduled to be seeded end to end. Water bars of rock placed at 100' intervals on roads, steep road leading down also has dirt water bar between each rock, bringing spacing to 50'. Lots have been bermed to hold water. All slopes scheduled for hydroseeding, no exact date of completion, pallets of tackifier on site. Ponds have not bee approved by ACHD. Pitrun on roads still not approved by ACHD.
|
General Inspection | 10/22/2019 | 10/22/2019 | 10/23/2019 | P | PASS |
Andy J. Long
|
|
|
Inpspection 10/25 PM
No trackout at either the upper or lower entrance. No muddy discharges or consistent fugitive dust issues observed.
Areas that are at grade have stabilization measures implemented, including tracking, slope interupting wattles, and hydroseeding. There are not many signs of growth yet in hydroseeded areas.
Lots in the finished areas have been terraced and have earthen berm containments to retain water on site. Roadway bases have been compacted but do not yet have pit run due to some pending ACHD approvals. To slow any water that may be flowing down the roads, 1.5 ft check dam/water bars have been installed. Areas that have been tracked will be hydoseeded this week, including above the new outlet pipe from the lower pond.
The site will continue winterization and installation of pipes and is hoping to begin work on the lower stormwater dams but they have not yet been approved by ACHD. If not approved, will need to consider additional temporary retention ponds and volume and velocity controls.
The sewer access road and area where drill rig did test holes will need stabilization measures if the ponds are not approved prior to the 1st week of November.
Follow up scheduled
|
Complaint Inspection | 10/14/2019 | 10/14/2019 | 10/15/2019 | A | PEND |
Andy J. Long
|
|
|
dust complaint on lower pond area and sewer acccess road.
Crew and drill rig has completed testing and demobilzed from site. No dust at time of inspection. The road which was formerly gravel has been disturbed and is dusty when vehicles drive over it. Need to install gravel or other stabilization method. Water truck application may also suffice. Will follow up with site to see what plan for this area is.
|
General Inspection | 10/9/2019 | 10/9/2019 | 10/11/2019 | P | PASS |
Andy J. Long
|
|
|
Inspection Wednesday 10-9
No trackout at entrances. Crew installing pipe on Vortex. Areas at final grade have had stabilization measures implemented.
Some areas of wattle installation are not staked properly, notified installation crew.
No corrections at this time. Will follow up with full site walk through
|
General Inspection | 9/30/2019 | 9/30/2019 | 9/30/2019 | P | PASS |
Michael Zawacki
|
|
|
Work hasn't begun on road for core drilling. Excavator crew working on bottom of road. Veasy has begun hydroseeding upper area. Water truck was on site spraying stockpiles. Outlet pipe on pond is armored.
|
Conference | 9/20/2019 | 9/20/2019 | 9/20/2019 | P | DONE |
Andy J. Long
|
|
|
Conference with site stormwater team to discuss corrections and upcoming plans at site:
- Construction entrance at Trent Point has been lengthened and widened. Street has been swept at entrance. - Storm drain inlet on Ridgepoint will not have any sediment protection installed due to previous overflows and erosion of sediment into the stormwater pond whch outfalls to the Mesa drainage channel that sends water to the Boise River. - The existing pond will be hydroseeded this month, the flow of stormwater passess over rip rap rock, and this rock channel with have wattle installed to keep sediment from the sides of the pond from getting into the rock. - Work will begin next week or the following to install a bypass pipe that will take stormwater from the exisitng subdivsion in the pond and divert it around the area that is to be disturbed for creation of new ponds for the new subdivsion. - Syman Co. has been working on maintaining all wattles and silt fences installed onsite, including repairing damaged silt below Vortex Drive - Hydroseeding for temporary and permanent stabilization will occur in October. - Roads will not get paved till next year, the road surface will be road mix to keep mud down and the roads will have stormwater controls installed to control direction of flow and velocity. - new construciton entrance to be installed at Ridgepoint by the pond for the upcoming activity in this area.
Will continue to monitor and inspect weekly.
|
General Inspection | 9/17/2019 | 9/17/2019 | 9/18/2019 | P | DEFR |
Michael Zawacki
|
|
|
EPA and IDEQ on site. Will follow up with contractor on inspection report.
|
Complaint Inspection | 9/10/2019 | 9/10/2019 | 9/10/2019 | P | DONE |
Michael Zawacki
|
|
|
Neighbor was concerned with work below road. Outlet for pond has been armored, some hillside disturbance. Talked to Syman on site about some new BMPs, sent pics and request to Steve requesting installation. Let concerned party know what I saw and my response.
|
General Inspection | 9/9/2019 | 9/9/2019 | 9/9/2019 | P | PASS |
Michael Zawacki
|
|
|
Post rainfall inspection. No esc issues with site. Did site walk through, no blowouts or rilling. Gravel bags and channel armoring completed on lower pond, no issue from rain. Upper section held all water, no blowouts down road on site. Sewer crew on site now, may have trackout issues at end of day.
|
General Inspection | 9/6/2019 | 9/6/2019 | 9/6/2019 | P | PASS |
Michael Zawacki
|
|
|
Post rainfall inspection, report of 1" rain in 20 minutes. RP on site with M3 reps. SOme damage to pond at lower entrance, issue was water jumped curb from road, not from site. Site absorbed water, no issues or blowouts. Syman on site checking BMPs, will add gravel bags to gutters. More entrance rock on site, water line will need to be tied in in middle of entrance, will fix entrance after that is completed. Will continue to clean streets of trackout.
|
Complaint Inspection | 9/5/2019 | 9/5/2019 | 9/5/2019 | P | FAIL |
Michael Zawacki
|
|
|
Message sent to RP. Suggest trying mag chloride or some sort of tackifier for haul road. Water trucks in use, causing trackout down road. Needs to be swept, some complaints about dust creasted by sweeper, may need to try vac sweeper. Suez crew working on water line, they are cutting through the edge of entrance.
|
Complaint Inspection | 8/29/2019 | 8/29/2019 | 8/29/2019 | P | PART |
Andy J. Long
|
|
|
fugitive dust complaint
- localized dust observed around equipmment movement. No wind blown dust occuring at time of inspection. Water truck onsite.
Lots of trackout and loose material on Trent Point. Will continue to monitor.
|
General Inspection | 8/26/2019 | 8/26/2019 | 8/26/2019 | P | FAIL |
Michael Zawacki
|
|
|
check on potential dust sources at site:
- rock grinding/trench digging? - loader traffic from lower to upper areas? - active grading areas? - pipe installation? - wind blown dust on temporarily inactive disturbed areas Met with all stakeholders at site. Dust is from haul road, trucks are turning in an area with silt a few inches deep. Two water trucks running, neither have sparayed area, they were going to get refilled and are supposed to be watering affected area. Construction entrance needs to be raked, starting to compact, lots of dust trackpit onto road, saw a dirt devil when the wind blew.
|
Complaint Inspection | 8/21/2019 | 8/22/2019 | 8/23/2019 | A | PEND |
Andy J. Long
|
|
|
dust complaint.- morning winds + acitivity causing large plumes visible from Parkcenter/Apple
Certain instances of uncotrolled dust is occuring at subdivsion. Request to have a truck that is only responsible for dust control along haul routes, stockpiles, and open disturbed areas where wind blown dust is occuring.
Currently there are 3 seperate crews with their own water truck. Trucks need to coordinate together to make sure areas are adequately sprayed with water. Request to start day with watering to soak in areas where work will occur. Crew noted that steep sections of haul roads cannot have too much water due to the heavy loads and traction.
Will continue to monitor, extra truck should be there for next week
|
General Inspection | 8/13/2019 | 8/15/2019 | 8/15/2019 | A | PART |
Andy J. Long
|
|
|
site walk-through 9 AM w/ Steve w/ CMG
No significant trackout or excessive fugitive dust at site during time of inspection (9 AM -11 AM). Site perimeter sediment barrier silt fence is installed and vegetation outside clearing limits has been preserved. Site has heavy duty construction entrance at Trent Point and permit signs are posted.
Corrections needed: - wattles installed must be overlapped per BMP specs in SWPPP or tightly abutted. Currently are loosely abutted and not thoroughly staked into ground. - construction entrance rock needs maintenance/refreshing - sweep loose dirt/dust out of gutters along Trent Point and Boulder Heights. - correction request to Central Paving to increase water truck circulation on the upper haul routes. Avoid spraying water near entrance and on steep sections of road (slippage hazard)
- request to provide update BMP site map to show current conditions. Include a site map to detail the grading and stabilization, showing active areas, temporary stabilized areas (with dates) and update permanent vegetation schedule in SWPPP.
- repair sections of silt fence damaged by rock fall at the lower road cut. Repair sections of wattle installed on finished grade slope that was driven over. Corrections issued to Steve with CMG and Rob with Central Paving
|
General Inspection | 8/2/2019 | 8/7/2019 | 8/8/2019 | A | PART |
Michael Zawacki
|
|
|
Wind is blowing towards neighborhood today. Two water trucks running on site, still some dust. Sand rock seperator also running and being water, causing some dust. Water trucks are still going to warm springs for water, no plan to bring tank to site. Some trackout, let foreman know that track pad needs to be cleaned. All workers parking on road. Major source of dust is lower haul road, has been saturated with water, dust is very fine. Site has lots of disturbed area and very loose dust, like talcum powder. 3 area of blasting remain. Some sort of temporary stabalization should be considered on idle areas.
|
General Inspection | 8/2/2019 | 8/2/2019 | 8/2/2019 | P | PASS |
Andy J. Long
|
|
|
WIP. Construction entance installed, work within the clearing limits and silt fence perimeter. Dust control trucks onsite. Walk through inspection scheduled for next week.
|
General Inspection | 7/18/2019 | 7/19/2019 | 7/22/2019 | A | CANC |
Andy J. Long
|
|
|
|
Tracking Control | 7/22/2019 | 7/22/2019 | 7/22/2019 | P | PASS |
Andy J. Long
|
|
|
check on construction entrance and dust control set up.
Construction entrance has been lengthened and Trent Point between entrance and Windsong has been well swept. No grading acitivity at time of inspection, crews working on putting in sewer lines. No trackout, no dust observed.
Wattle installed on the slope above the entrance have been removed to install run-on diversion channel above the slope and new road. After installation, slope will be spread with top soil, tracked, and slope interupting wattles installed.
Sweeper needs to hit gutter on Windsong between Boulder Heights and Birdsong.
|
Tracking Control | 7/15/2019 | 7/16/2019 | 7/16/2019 | P | FAIL |
Andy J. Long
|
|
|
Construction entrance has been widened but there is still trackout and and loose dirt on Trent Point.
Corrections in progress: - going to install access to water so they can fill onsite tanks, water trucks will no longer need to leave site. Central Paving and L2 are supposed to have water trucks operating for dust control and compaction. - construciton entrance rock should be roughened each day for maintenance. Access should set up so that all exiting traffic must travel over the full length of the trackpad.
Follow up scheduled.
|
General Inspection | 7/11/2019 | 7/12/2019 | 7/12/2019 | A | PART |
Michael Zawacki
|
|
|
Lots of trackout down hill. Talked to foreman and they will get it swept and entrance improved. They are working on getting a water tank at site so they don't need to drive down to Warm Springs to fill up.
|
Complaint Inspection | 7/8/2019 | 7/8/2019 | 7/9/2019 | P | FAIL |
Andy J. Long
|
|
|
complaint received 7/5 - dust issues at construction entrance.
notifired RP 7/5 to sweep up all loose dirt on Trent Point to Windsong. Follow up at site.
Corrections needed:
- do maintenance on construction entrance. Rough up rock, add rock, make rock go to edge of Trent Point and lengthen. Prevent truck and works from driving around rock entrance.
- sweep up gutter on Windsong from Birdsong to Trent Point.
|
General Inspection | 7/2/2019 | 7/2/2019 | 7/2/2019 | P | PART |
Andy J. Long
|
|
|
Inspection conducted Thursday 6/27
- Boise ESC permit posted, SWPPP binder onsite. No significant trackout, no disharges occuring. Dry, sunny weather with light wind. - WIP on rough grading and utilitity installation. - Rock construction entrance installed, some trackout due to trucks exiting without driving over the track pad. Site has a sweeper unit onsite that is used at end of each day. - No breaches in silt fence perimeter observed - Vegetation between graded areas and SF has been preserved - Slopes along the Trent Point entrance have been tracked, wattles installed, and some areas hydroseeded. - Hydroseeded areas without wattles are areas with a less steep slope - Water truck working site on haul routes to keep down dust. They request water truck to stop watering about 200 M from the construction entrance due to the trackout it was causing. No dust leaving site boundaries, no consisent plumes
Correction requests to Andy w/ Syman and Steve with CMG. - make sure wattles installed are along contours, staked every 4-5 feet, and trenched in. Request for overlap, some wattle interrsections are tightly butted instead. Some sections on upper slope above entrance are > 8 ft apart and not aligned with contour. - Make changes at entrance to make sure equipment exiting site uses the track pad. Suggested fencing or signages, wider rock area
|
General Inspection | 6/11/2019 | 6/11/2019 | 6/11/2019 | P | PASS |
Michael Zawacki
|
|
|
Water truck on site, no blowing dust. No trackout or ESC issues.
|
General Inspection | 5/29/2019 | 5/29/2019 | 5/29/2019 | P | PASS |
Michael Zawacki
|
|
|
Silt fence has been repaired where it wasn't trenched. DIversion added to road to deflect stormwater into vegetation. Silt fence added below road to catch any water flow, wattle added below to catch additional sediment and water as needed. Graded areas on hill have been tracked and wattle installed.
|
General Inspection | 5/23/2019 | 5/23/2019 | 5/23/2019 | P | PEND |
Michael Zawacki
|
|
|
Met with Syman crew on site. SOme areas of wire back silt fence have been undercut and need repair. End of road cut in acting as channel, asked for a few tiers of wattle going down hill and also below silt fence in case of failure. They need to get more materials and will be back. Asked to have done before rain event anticipated 5-24.
|
Tracking Control | 5/15/2019 | 5/17/2019 | 5/17/2019 | A | PASS |
Michael Zawacki
|
|
|
No activity during rain. Street has been swept, new load of rock has been brought to extend and redirect etrance. Large buffer before silt fence, water staying on excavated area, berm in place.
|
General Inspection | 5/13/2019 | 5/13/2019 | 5/15/2019 | P | PART |
Michael Zawacki
|
|
|
No dust issues with grading. Still not much disturbed area. Some trackout. Entrance is being avoided, needs to be expanded. Message and picture sent to RP, follow up scheduled.
|
Site Preparation | 5/1/2019 | 5/3/2019 | 5/3/2019 | A | PASS |
Andy J. Long
|
|
|
Initial BMPs installed:
- wire back perimeter silt fence installed properly - lined heavy duty recycled concrete construction entrance installed. - ESC permit sign and SWPPP board posted at entrance.
Crew beginning to excavate areas to move rock piles at Trent Point to new area and dig temporary clay lined water holding pond. Water to be used for compaction and dust control.
No corrections requested.
|
Site Preparation | 5/1/2019 | 5/1/2019 | 5/1/2019 | A | DONE |
Andy J. Long
|
|
|
10 AM pre-con meeting
|